Parameters should always be adjusted during normal operation with the door in the "CLOSED"
position, because the controller then accepts the values immediately.
Taking the counterweights into account, the maximum static closing force must not exceed
150 N!
Risk of injury through moving mechanical parts
After the elevator door has been commissioned, the permitted energies and forces on the
heaviest door in the entire (elevator) system must be checked by service personnel with
landing door and cabin door coupled, and adjusted if they exceed their limit values.
Gearing up or down is not allowed on the toothed belt because this would change the
kinetic energies or static forces on the door. The door width would then no longer be valid.
Note
After the optimal parameter settings have been determined, they can be noted in the
configuration record (see Appendix Settings record (Page 36)). This record should also be
kept at hand when asking questions on the Hotline.
Elevator door drive AT12
Equipment Manual, 06/2020, A2B00086683-AD
CAUTION
WARNING
Electric adjustment and commissioning
19