Carrier 30WG Operation Instructions Manual page 22

Touch pilot junior control
Table of Contents

Advertisement

Pump Configuration Menu – PUMPCONF (continued)
No.
Point name
Status
5
6
7
8
clpmpdel
24 to 3000
9
clpmpper
no / yes
10
clpmpsby
no / yes
11
clpmploc
no / yes
12
13
cdpmpseq
0 to 4
14
15
16
17
18
19
cdpmpdel
24 to 3000
20
cdpmpper
no / yes
21
cdpmpsby
no / yes
22
cdpmploc
no / yes
23
ol_pump
no / yes
*Depends on the selected language (English by default).
Heat/Cool Config Menu – HCCONFIG
No.
Point name
Status
1
cr_sel
0 to 3
2
hr_sel
0 to 3
3
4
5
boil_on
no / yes
6
boil_th
-15 to 15
7
ehs_th
-4.90 to 21.42
8
both_sel
no / yes
9
ehs_back
no / yes
10
ehs_pull
0 to 60
*Depends on the selected language (English by default).
HDC Configuration Menu – HDC_CONF
No.
Point name
Status
1
adpmpper
no / yes
2
summ_oat
15.0 to 30.0
3
summ_on
0 to 12
4
summ_off
0 to 12
22
Default
Unit
Displayed text*
2 = Two Pumps Auto
3 = Pump#1 Manual
4 = Pump#2 Manual
48
hour
Pump Auto Rotation Delay
no
-
Cool Pump Anti-Sticking
no
-
Cool Pump Stopped in Sby
no
-
Flow Checked if Pump Off
CONDENSER PUMP
0
-
Condenser Pumps Sequence
0 = No Pump
1 = One Pump Only
2 = Two Pumps Auto
3 = Pump#1 Manual
4 = Pump#2 Manual
48
hour
Pump Auto Rotation Delay
no
-
Cond Pump Anti-Sticking
no
-
Cond Pump Stopped in Sby
no
-
Flow Checked if Pump Off
no
-
Open loop pump Control
Default
Unit
Displayed text*
0
-
Cooling Reset Select
0
-
Heating Reset Select
0=none, 1=OAT,
2=delta T, 3=4-20mA
no
Boiler Manual Command
-10
°C
Boiler OAT Threshold
5.2
°C
Elec Stage OAT Threshold
no
-
HSM Both Command Select
no
-
1 Elec Stage for Backup
0
min
Electrical pulldown time
Default
Unit
Displayed text*
no
-
Add. Pump Anti-Sticking
20.0
°C
Summer OAT threshold
5
hour
Summer OAT start delay
5
hour
Summer OAT stop delay
Description
2 = Two Pumps Auto (units with two pumps)
3 = Pump#1 Manual
4 = Pump#2 Manual
Pump auto rotation delay (units with two
pumps = auto control)
Evaporator pump anti-sticking protection
Not applicable (please ignore this parameter)
Water flow is checked when the pump is off
CONDENSER PUMP
Condenser pump sequence
0 = No Pump
1 = One Pump Only
2 = Two Pumps Auto (units with two pumps)
3 = Pump#1 Manual
4 = Pump#2 Manual
Pump Auto Rotation Delay (units with two
pumps = auto control)
Condenser pump anti-sticking protection
Not applicable (please ignore this parameter)
Water flow is checked when the pump is off
Open loop pump control
Description
Cooling reset selection
Heating reset selection
0 = None, 1 = OAT,
2 = Delta T, 3 = 4-20 mA control
Boiler manual command:
No = boiler control based on OAT control logic
(see boil_th below)
Yes = boiler control enabled if OAT sensor is
NOT present or the sensor fails
Boiler OAT threshold
Electric heating stage, OAT threshold
HSM both command selection
One electric heating stage used for back-up
Electrical pull-down time
Description
Additional pump anti-sticking protection
This threshold defines when Summer mode
can be started
Summer mode is activated if OAT is above
OAT Threshold [sum_oat] for at least the
sum_on delay
Summer mode is reset when OAT goes below
OAT Threshold [sum_oat] minus 2K for at least
the sum_off delay