CADDY PF01015 Installation And Operating Instructions Manual page 43

Table of Contents

Advertisement

OUTPUT
MODEL
(CFM)
950
15 kW
1,300
950
18 kW
1,300
950
20 kW
1,300
WOOD
Electrical connections must conform to the wiring diagram supplied with the option.
The electrical element must be connected to the power board (See Section 22 - ELECTRICAL DIAGRAM FOR
ELECTRIC UNIT). For security reasons, the electrical element has a manual reset thermostatic sensor that is located
inside the electrical unit. If the temperature of the electric unit exceeds the high limit, the thermostatic sensor will
disengage the elements. After finding and fixing the problem that has caused the unit to overheat (static pressure too
high, fan breakdown, etc.), reactivate by pressing the red "manual reset" button on the thermostatic sensor (L-170
thermodisc).
L-170 Thermodisc RESET
TEMP. VAR.
TOTAL AMPERAGE
BTU/H
(OF)
50
36
51195
60
44
61434
67
49
68260
ALIMENT.
BREAKER
CALIBRE
75
100
87
125
95
125
15
VOLTAGE
# OF ÉLÉMENTS
1 PHASE
4
120/240
3 – 5 kW
2 – 5 kW,
4
120/240
2 – 4 kW
3
120/240
4 – 5 kW
120
Red button manual reset