OPTION 3 and OPTION 4 are permitted when installing the Caddy furnace with en existing furnace whose hot air
plenum ducts are downwards flowing. The hot air plenum of the Caddy furnace must be above the furnace and cannot
be directed downward.
Do not install connecting ducts in a way that would allow inversion of the air flow (see example 1 and 3).
The transfer duct between the existing furnace and the add-on must be at least 435 square inches (0.28 m
deviations radius must be at least 6" (152 mm). (See OPTION 1 and 2).
Option 1
Option 2
*Minimum duct size 435
square inches (0.28 m
*R = Minimum radius 6 inches
) and
2
2
)
15