Sensors & External Input; Configuration; Monitoring - Honeywell TR80UWD Installation And Operating Manual

Wall module
Table of Contents

Advertisement

3.5 SENSORS & EXTERNAL INPUT

3. 5. 1 Configuration

Register
type
Holding
Holding
Holding

3. 5. 2 Monitoring

Register
type
Input
Input
Input
Unit and scale of the external sensor input depend on configured signal type:
Raw ohms
NTC
Voltage (0-10V or 2-10Vdc)
NO contact
NC contact
Temperature values on Modbus are always in degrees Celsius, even if the user has selected
Fahrenheit for display.
TR80 - Installation and Operation Guide
Relative
Absolute
Address
Address
2011
42012
2012
42013
2013
42014
Relative
Absolute
Address
Address
5
30006
6
30007
7
30008
Configuration
Ohms
°C
Percent
0=open, 1=closed
0=closed, 1=open
Config
Dir
Name
parameter
External
R/W
sensor
13
type
On-board
sensor
R/W
14
temp
offset
On-board
sensor
R/W
15
humidity
offset
Dir
Name
R
External input measured value
R
Onboard temp sensor measured value °C
Onboard humidity sensor measured
R
value
Unit
Scale
1
0.1
0.1
Unit
Range
Scale
0: NONE
1: NO contact
2: NC contact
3: 0-10 Vdc
enum
4: 2-10 Vdc
5: Raw Ohms
6: NTC10K
7: NTC20K
K
-10.0 ... +10.0 K 0.1
%Rh
-10 ... +10 %Rh 1
Unit
Scale
See below
See below 0
0.1
%Rh
1
Default
value
0
0
0
Default
value
0
0
38