3. 12. 2 Blind Group 1 control parameters

Register
type
Holding
Holding
Input
Input
'Position Feedback' and 'Angle Feedback' information typically come from the master control-
ler. When the user enters the setting mode for any blind, these are the values that will be dis-
played initially, and the user will start setting (incrementing / decrementing) from these
values.
The 'New Position' and 'New Angle' registers are used to convey user commands. These will
normally be at an invalid value of 32767. If the user adjusts the position or angle on the wall
module, the relevant register will contain the newly set value. But as soon as it is read over
Modbus, it will automatically revert to the invalid value of 32767. This scheme ensures all user
commands are registered as a change-of-value and can be acted upon by the master control-
ler.
3. 12. 3 Blind Group2 Configuration & Control Parameters
The Blind 2 configuration parameters are as shown below.
Register
type
Holding
Holding
Holding
Holding
Holding
The Blind 2 control parameters are as shown below.
Register
type
Holding
Holding
Input
Input
55
Relative
Absolute
Address
Address
1400
41401
1401
41402
400
30401
401
30402
Relative
Absolute
Dir
Address
Address
2408
42409
R/W
2409
42410
R/W
2410
42411
R/W
2411
42412
R/W
2412
42413
R/W
Relative
Absolute
Address
Address
1402
41403
R/W
1403
41404
R/W
402
30403
R/W
403
30404
R/W
Dir
Name
R/W
Blind 1 position feedback
R/W
Blind 1 angle feedback
R/W
Blind 1 new position
R/W
Blind 1 new angle
Config
Name
parameter
Blind 2 type
408
Blind 2 min
409
pos
Blind 2 max
410
pos
Blind 2 min
411
angle
Blind 2 max
412
angle
Dir
Name
Blind 2 position feedback
Blind 2 angle feedback
Blind 2 new position
Blind 2 new angle
TR80 - Installation and Operation Guide
Unit
Range
%
0-100%
°
-180...+180°
%
0-100%
°
-180...+180°
Unit
Range
Bit 0: angle control
bitwise
Bit 1: position direct/
reverse
%
0...100%
%
0...100%
°
-180°...180°
°
-180°...180°
Unit
Range
%
0-100%
°
-180...+180°
%
0-100%
°
-180...+180°
Default
value
50%
0
32767
32767
Default
value
1
0%
100%
-80°
+80°
Default
value
50%
0
32767
32767