24 Volt Thermostat Wiring - Non-Communicating Thermostat
Connections
NOTE: Wire routing must not interfere with the circulator blower
operation or routine maintenance.
The air handler's integrated control module provides terminals
for "Y1" and "Y2" and "W1" and "W2" thermostat connections.
This allows the air handler to support the systems shown in
the following table. Refer to the following figures for typical
connections to the integrated control module. Thermostat wiring
entrance holes are located in the top of the blower. Wire routing
must not interfere with circulator blower operation or routine
maintenance.
NOTE: A removable plug connector is provided with the control
to make thermostat wire connections. This plug may be removed,
wire connections made to the plug, and replaced. It is strongly
recommended that you do not connect multiple wires into a single
terminal. Wire nuts are recommended to ensure one wire is
used for each terminal. Failure to do so may result in intermittent
operation.
COOLING HEAT PUMP HEATING ELECTRIC HEATING
1-STAGE
------
2-STAGE
------
1-STAGE
1-STAGE
2-STAGE
2-STAGE
1-STAGE
1-STAGE
2-STAGE
2-STAGE
Typical Single-Stage Cool,
Single-Stage Heat Thermostat
R C G
W1
1
2
R C G
W1
W2
R C
Remote Condensing Unit
(Single-Stage AC)
Typical Single-Stage Cooling with Single-Stage Heating
1- or 2-STAGE
1- or 2-STAGE
------
------
1- or 2-STAGE
1- or 2-STAGE
Place Jumper Between Y1
and O for Proper
Dehumidification Operation
and Proper Ramping
Y1
Profile Operation
Air Handler Integrated
O
Y1
Y2
Control Module
DEHUM
Y
NEU
Dehumidistat
HOT
[Optional]
Figure 14
Typical Two-Stage Cool,
Two-Stage Heat Thermostat
R C G
W1 W2 Y1
1
2
R C G
W1 W2 Y1
R C
Remote Condensing Unit
(Two-Stage AC)
TYPICAL TW0-STAGE COOLING WITH TWO-STAGE
R C G
W/E
1
2
R C
G
W1 W2 Y1
R C
W1
Remote Condensing Unit
(Single-Stage HP)
Typical Single-Stage Heat Pump with
Auxiliary/Emergency Heating
R C G
W/E
1
2
R C
G
W1 W2 Y1
R C
W1
Remote Condensing Unit
(Two-Stage HP)
Typical Two Stage Heat Pump heating and
Auxiliary/Emergency Heating
The optional usage of a dehumidistat allows the air handler's
circulator blower to operate at a slightly lower speed during
a combined thermostat call for cooling and dehumidistat call
for dehumidification. This lower blower speed enhances
dehumidification of the conditioned air as it passes through the
AC coil. For proper function, a dehumidistat applied to this air
handler must operate on 24 VAC and utilize a switch which opens
on humidity rise.
13
Place Jumper Between Y1
and O for Proper
Dehumidification Operation
and Proper Ramping
Y2
Profile Operation
Air Handler Integrated
O
Y2
Control Module
DEHUM
Y1
Y2
NEU
Dehumidistat
HOT
[Optional]
HEATING
Figure 15
Typical Single-Stage Cool,
O
Y1
Single-Stage Heat
Heat Pump Thermostat
Air Handler
O
Integrated Control Module
Y2
DEHUM
O
Y
NEU
HOT
Figure 16
Typical Two-Stage Cool,
O
W2 Y1
Y2
Two-Stage Heat
Heat Pump Thermostat
Air Handler
O
Y2
Integrated Control Module
DEHUM
O
Y1
Y2
NEU
HOT
Figure 17
Dehumidistat
[Optional]
Dehumidistat
[Optional]