6.10 Setting the Alarm Delay Duration

Procedure
Explanation
6-10
This section explains the details of setting the duration of the delay alarm.
1.
Hold down the
2.
Press the
key or SHIFT +
key.
3.
Press the
key or SHIFT +
the
key.
4.
Set each item and press the
Use the
key or SHIFT +
For the procedure on how to enter values or characters, see section 4.2.
If you press the ESC key in the middle of the operation, the settings entered up
to then are cancelled, and the display returns to a higher level menu.
5.
When the Setting complete screen appears, do either of the following:
Press the
key to set other channels.
If you are done, press the ESC key.
6.
Hold down the
Set=Aux
Aux=Alarm delay time
CH=01-01
Last channel
First channel
Duration=
01-01 Channel
Setting complete
ESC/?
Duration
The duration can be set to a value in the range of 1 to 3600 s.
However, the alarm delay time is an integer multiple of the scan interval. For example, if
the scan interval on the dot model is 2.5 s, the actual duration is an integer multiple of
2.5 s. If the set value is not equal to an integer multiple of 2.5 s, the duration is the
smallest integer multiple of 2.5 s greater than the set value.
Example: The actual duration for 1 s and 2 s is 2.5 s.
<Related Topics>
Enabling the alarm delay function: Section 7.15
key for 3 seconds to enter Setting mode.
MENU
key to select Aux and then press the
key to select Alarm delay and then press
key.
key to select values.
key for 3 seconds to return to Operation mode.
MENU
Set the channel range.
10
Set the alarm delay time.
The new setting takes effect.