Assembly And Installation - Delta LYTE II DRL-480W Series Manual

Table of Contents

Advertisement

PRELIMINARY DATASHEET- For product review purpose only. The specs are subjected to change.
LYTE II DIN Rail Power Supply
DRL-480W series / DRL-V480W1EN
Assembly & Installation
The power supply unit (PSU) can be mounted on 35 mm DIN rails in accordance with EN 60715. The device should be installed with
input terminal block at the bottom.
Each device is delivered ready to install.
Mounting
Fig. 3.1 Mounting
Snap on the DIN rail as shown in Fig. 3.1:
1.
Tilt the unit upwards and insert it onto the DIN rail.
2.
Push downwards until stopped.
3.
Press against the bottom front side for locking.
4.
Shake the unit slightly to ensure that it is secured
Safety Instructions
Vertical Mounting
All parameters are specified at 25°C ambient and AC input unless otherwise indicated.
9
www.DeltaPSU.com (August 2021, Rev. X00)
Dismounting
Fig. 3.2 Dismounting
To uninstall, Delta provides an easy way to pull or slide down the
latch with screw driver as shown in Fig. 3.2. Then slide the power
supply unit (PSU) in the opposite direction, release the latch and
pull out the power supply unit (PSU) from the rail.
ALWAYS switch mains of input power OFF before connecting and
disconnecting the input voltage to the unit. If mains are not turned OFF,
there is risk of explosion / severe damage.
To guarantee sufficient convection cooling, keep a distance of 40 mm
(1.57 inch) above and 20 mm (0.79 inch) below the device as well as a
lateral distance of 5 mm (0.2 inch) to other units and if load less than
50%, lateral distance can be 0 mm. In case the adjacent device is a
heat source, the lateral distance will be 15 mm (0.6 inch).
Note that the enclosure of the device can become very hot depending on
the surrounding air temperature and load of the power supply. Risk of burns!
The main power must be turned off before connecting or disconnecting
wires to the terminals.
DO NOT insert any objects into the unit.
Hazardous voltages may be present for up to 5 minutes after the input
mains voltage is disconnected. Do not touch the unit during this time.
The power supplies are built in units and must be installed in a cabinet or
room (condensation free environment and indoor location) that is relatively
free of conductive contaminants.