Delta LYTE II DRL-480W Series Manual page 3

Table of Contents

Advertisement

PRELIMINARY DATASHEET- For product review purpose only. The specs are subjected to change.
LYTE II DIN Rail Power Supply
DRL-480W series / DRL-V480W1EN
Model Number
Mechanical
Case Cover / Chassis
Dimensions (L x W x D)
Unit Weight
Indicator
Cooling System
Terminal*
4
Wire
Mounting Rail
Noise (1 Meter from power supply)
*4 The torque at the terminal connector shall not exceed 4Kgf.cm. (3.47 lbf.in).
Environment
Surrounding Air
Temperature
Power De-rating
Operating Humidity
Operating Altitude
Shock Test
Vibration
Over Voltage Category
Pollution Degree
Protections
Overvoltage
Overload / Overcurrent
Over Temperature
Short Circuit
Protection Against Shock
*5 Constant current limit protection for inductive and capacitive load applications
*6 PE: Primary Earth
All parameters are specified at 25°C ambient and AC input unless otherwise indicated.
3
www.DeltaPSU.com (August 2021, Rev. X00)
DRL-24V480W1EN
Aluminum
123.6 x 56 x 116.8 mm (4.87 x 2.2 x 4.60 inch)
0.87 kg (1.91 lb)
Green LED (DC OK)
Convection
Input
3 Pins (Rated 300V/30A)
4 Pins (Rated 300V/30A)
Output
Input
AWG 18-12 (Current rating can refer to "AWG Wire Table")
Output
AWG 18-12 (Current rating can refer to "AWG Wire Table")
Standard TS35 DIN Rail in accordance with EN 60715
Sound Pressure Level (SPL) < 25 dBA
Operating
-30°C to +70°C (-40°C Cold Start)
Storage
-40°C to +85°C
> 40°C de-rate power by 1.67 % / °C @ 115 Vac
Temperature
> 50°C de-rate power by 2.5 % / °C @ 230 Vac
Input
< 100Vac de-rate power by 1% / Vac
Voltage
20 to 90% RH (Non-Condensing)
0 to 5,000 Meters (16,400 ft.)
IEC 60068-2-27, Half Sine Wave: 50 G for duration of 11 ms; 3 times per direction,
Non-
Operating
9 times in total
Operating
IEC 60068-2-27, Half Sine Wave: 10 G for duration of 11 ms; 1 time in X axis
IEC 60068-2-6, Random: 5 Hz to 500 Hz (2.09 G);
Non-
Operating
20 min per axis for all X, Y, Z direction
IEC 60068-2-6, Sine Wave: 10 Hz to 500 Hz; 3 G peak;
Operating
60 min per axis for all X, Y, Z directions
II (Compliance to EN 62477-1 OVC III with 2000 meters altitude)
2
<34.0 V, SELV Output,
Latch Mode
105 - 150% of rated load current, Auto-recovery
Continuous current limit Mode*
Latch Mode
Hiccup Mode, Non-Latching
(Auto-Recovery when the fault is removed)
Class I with PE
5
(Vo > 80%)
*6
connection
DRL-48V480W1EN
<68.0 V, SELV Output,
Latch Mode

Advertisement

Table of Contents
loading

This manual is also suitable for:

Lyte ii drl-v480w1en seriesLyte ii drl-24v480w1en