PRELIMINARY DATASHEET- For product review purpose only. The specs are subjected to change.
LYTE II DIN Rail Power Supply
DRL-480W series / DRL-V480W1EN
Model Number
EMC
Emissions (CE & RE)
Component Power
Supply for General Use
Immunity
Electrostatic
Discharge
Radiated Field
Electrical Fast
Transient / Burst
Surge
Conducted
Power Frequency
Magnetic Fields
Voltage Dips and
IEC 61000-4-11
Interruptions
Harmonic Current
Emission
Voltage Fluctuation and
Flicker
Voltage Sag Immunity
SEMI F47 – 0706
1) Criteria A: Normal performance within the specification limits
2) Criteria B: Temporary degradation or loss of function which is self-recoverable
3) Criteria C: Output out of regulation, shuts down during test (Need to recycle AC power cord to normal operation after test)
4) Asymmetrical: Common mode (Line to earth)
5) Symmetrical: Differential mode (Line to line)
All parameters are specified at 25°C ambient and AC input unless otherwise indicated.
5
www.DeltaPSU.com (August 2021, Rev. X00)
DRL-24V480W1EN
CISPR 32, EN/BS 55032, EN/BS 61000-6-4, AS/NZS CISPR32, EN/BS EN/BS 61204-3, KN32
Compliance to FCC Title 47, EN/BS 61000-6-3: Class B
EN/BS EN 61204-3
EN 55035, KN35, EN/BS 61000-6-2
Compliance to EN/BS 61000-6-1
IEC 61000-4-2
Level 4 Criteria A
Air Discharge: 15k V
Contact Discharge: 8 kV
IEC 61000-4-3
Criteria A
1)
80 MHz – 1 GHz, 10 V/M, 80% Modulation (1 kHz)
1.4 GHz – 6 GHz, 3 V/M, 80% Modulation (1 kHz)
2 GHz – 2.7 GHz, 1 V/M, 80% Modulation (1 kHz)
IEC 61000-4-4
Level 3 Criteria A
2 kV
IEC 61000-4-5
Level 4 Criteria A
Common Mode
Differential Mode
IEC 61000-4-6
Level 3 Criteria A
150 kHz – 80 MHz, 10 Vrms
IEC 61000-4-8
Level 4 Criteria A
30 A/m
0% residual; 1 cycle, Criteria B
40% residual; 10 cycle, Criteria C
70% residual; 25 cycle, Criteria C
IEC/EN/BS 61000-3-2, Class A
IEC/EN/BS 61000-3-3
80% of 200 Vac
70% of 200 Vac
50% of 200 Vac
1)
1)
1)
4)
: 4 kV
5)
: 2 kV
1)
1)
2)
3)
3)
160 Vac, 1000 ms
140 Vac, 500 ms
100 Vac, 200 ms
DRL-48V480W1EN
Criteria A
1)
Criteria A
1)
Criteria A
1)