UPS5000-H-(1200 kVA-1600 kVA) Quick Guide (100 kVA Power Modules, Three-Phase Three-Wire)
Securing the Cabinets (1600 kVA)
Power cabinet 1
Power cabinet 2
Bypass cabinet
unit: mm
A: mounting holes on the channel
steel
B: mounting holes on the floor
Inductor cabinet
M12 bolt
Spring washer
Flat washer
Expansion sleeve
Expansion nut
Concrete floor
4
Before combining cabinets, remove
the screws preinstalled on the copper
bars in power cabinet 2. Store them
properly for future use.
Remove the rear door of
power cabinet 1 when
installing cabinet
combination screws in the
middle at the rear.
•
Installing rectifiers in the inductor cabinet.
•
Rectifiers are delivered separately, and
baffle plates are placed in the fitting bag
of the inductor cabinet.