Product Loading; Unit Operation And Components; Electronic Temperature Control - Master Bilt BGR15 Installation And Operation Manual

Table of Contents

Advertisement

PRODUCT LOADING

The BGR series of units are not intended to be a pull down refrigerator and as such the product must be
loaded at their intended merchandising temperature.
Before loading products, allow the equipment to operate empty for at least two
hours.
When loading products:
- Do not block the lower ventilation grille with the packages about to be loaded.
- Do not over hang the shelf.
- Do not press the product against the rear wall
- Never exceed the shelf weight limits

UNIT OPERATION AND COMPONENTS

ELECTRONIC TEMPERATURE CONTROL:

The unit is provided with an electronic temperature control that controls the operation of the unit based
on the temperature of the air discharging from the evaporator at the back of the unit.
In order to achieve the desired product temperature, the electronic control is factory adjusted to hold
product at 35º – 38ºF.
When you plug the unit in, the control display will
illuminate. However, there is a start-up delay of 2
minutes before the compressor(s) are energized. This
delay avoids the possibility that during a power failure
the compressors are forced to restart before the
refrigerant pressures are equalized.
The control has been factory-adjusted with a defrosting
cycle that is scheduled to ensure that the evaporator
performs without any ice build-up.
None of the factory-programmed electronic control parameters can be modified unless an access code is
entered (contact Master-Bilt technical service for this code).