Ac110V Input Extension Block; Input Circuit Connection - Mitsubishi Electric Melsec-F FX2NC Series Hardware Manual

Programmable controllers
Table of Contents

Advertisement

FX2NC Series Programmable Controllers
5.2

AC110V input Extension block

Table 5.3 : FX
Input voltage
Input impedance
Input current
OFF
ON/ON
Response time
Circuit isolation / Operation indication
5.2.1

Input circuit connection

Figure 5.6 : FX
85-132 V AC
50/60 Hz
COM1
X0
X1
X2
-8EX-UA1/UL, FX
-8EX-UA1/UL input specification
0N
2N
OFF; input switching current 80V 3.8mA/30V 1.7mA
-8EX-UA1/UL, FX
0N
2N
85-132V AC 50/60Hz
21kΩ/50HZ 18kΩ/60Hz
4.7mA 100V AC/50Hz 6.2mA 110V AC/60Hz
25ms
Photocoupler/LED is lit
-8EX-UA1/UL
Inputs 5.
5-8