E-Stop Safety Modules with Fixed Delay –
Front Cover Plate
The same screwdriver is handy for
turning the rotary Delay Time selector
switches and for setting the DIP switches.
Figure 5. Use a screwdriver to gently pry
the cover loose from the Module
housing.
DIP AND SELECTOR SWITCH SETTINGS
(REMOVE COVER, FACTORY SETTINGS SHOWN)
DELAY OFF TIME FOR CONTACTS
37 - 38, 47 - 48, 61 62.
MODEL
DELAY
ES-TN-1H1
0.25s
ES-TN-1H2
0.5s
ES-TN-1H3
1.0s
ES-TN-1H4
2.0s
ES-TN-1H7
4.0s
ES-TN-1H8
6.0s
ES-TN-1H9
8.0s
ES-TN-1H10
10.0s
ES-TN-1H11
15.0s
ES-TN-1H12
20.0s
S1
S2 S3 S4
S1.1
S2.1 S3.1S4.1
1
1
1
1
1
1
0
0
0
0
0
0
S1
S1.1 S2 S2.1 S3 S3.1 S4 S4.1
1
1
AUTO RESET
MANUAL
0
0
RESET
2 CHANNEL
1
1
MONITORING
1 CHANNEL
0
0
MONITORING
AUTO
POWER UP
MANUAL
POWER UP
1 CH. INPUT
2 CH. INPUT
Figure 6. Module DIP switches and
selectors, set to factory settings
Banner Engineering Corp.
Minneapolis, MN U.S.A.
www.bannerengineering.com • Tel: 763.544.3164
The DIP switches and selector switches are located inside the Module housing, behind
the front plate. Before adjusting any settings, turn OFF power to the Module. Remove
the front plate by using a screwdriver in the slot on the right side and gently prying the
cover away from the housing (Figure 5). Turn the rotary Delay Time selector switches
to the desired position using the same small screwdriver in the slot on the arrow. Use
the screwdriver blade to slide the DIP switches to their proper positions also.
The corresponding pairs of DIP switches and the two rotary Delay Time selector
switches must match at all times, or a Fault condition will result. (If this occurs, turn the
power OFF, adjust the pairs of switches to match, and turn the power supply back ON.)
Figure 6 shows the DIP switches and Delay Time selector switches properly set for No
Delay, Manual Reset, 1-Channel Monitoring, Manual Power-Up, and 2-Channel Input.
The E-Stop Safety Module factory settings are as follows:
Manual/Auto Reset (S1, S1.1)
1-/2-Channel Monitoring (S2, S2.1)
Manual/Auto Power-Up (S3, S3.1)
2-/1-Channel E-Stop (S4, S4.1)
!
It is possible for the OFF-delay timing
function to fail, due to circuit failure
or power loss, resulting in premature
opening of the delay contacts. The
1
1
installation, including its wiring, must
be designed to prevent any hazard
0
0
which could result from the loss of a
programmed output switching delay
time.
1
1
0
0
1
1
0
0
DIP-Switch and Selector Switch Settings
Switch
Factory Setting
0 – Manual reset
0 – 1-Channel Monitoring
0 – Manual power-up
0 – 2-Channel E-stop
WARNING . . .
Consequence of
OFF-Delay Failure
Models ES-TN-1H..
Optional Setting
1 – Auto reset
1 – 2-Channel Monitoring
1 – Auto power-up
1 – 1-Channel E-stop
WARNING . . .
!
After
Switch Configuration
Follow the complete checkout and
troubleshooting procedure (see page 12)
following any change in the settings to
the DIP switches.
P/N 61061 rev. A