Download Print this page

General Meter Specifications; Installing The Meter - red lion PAXLR-PAX Quick Start Manual

Lite rate meter

Advertisement

G
M
ENERAL
1. DISPLAY: 6-digit, 0.56" (14.2 mm), 7-segment red LED.
Decimal points are programmed by front panel keys.
2. POWER:
AC Power: 115/230 VAC, switch selectable. Allowable power line variation
±10%, 50/60 Hz, 6 VA. @ 100 mA max.
Isolation: 2300 Vrms for 1 min. to input and DC Out/In.
DC Power: 10 to 16 VDC @ 0.1 A max.
3. SENSOR POWER: 9 to 17.5 VDC @ 100 mA max.
4. KEYPAD: 3 programming keys, the  (Down Arrow) key can also function
as the front panel reset button.
5. INPUT: (DIP switch selectable)
Accepts pulses from a variety of sources including NPN-OC, PNP-OC, TTL
Outputs, Magnetic Pickups and all standard Red Lion sensors.
Logic: Input trigger levels V
= 1.5 V max.; V
IL
Current Sinking: Internal 7.8 K pull-up to +12 VDC, I
Current Sourcing: Internal 3.9 K pull-down, 8 mA max. @ 30 VDC max.
MAGNETIC PICK-UP:
Sensitivity: 200 mV peak
Hysteresis: 100 mV
Input impedance: 3.9K @ 60 Hz
Maximum input voltage: ±40 V peak, 30 Vrms
6. INPUT FREQUENCY RANGE:
Max Frequency: 25 KHz
Min Frequency: 0.01 Hz
Accuracy: ±0.01%
2
7. MEMORY: Nonvolatile E
PROM retains all programmable parameters and
display values.
8. ENVIRONMENTAL CONDITIONS:
Operating Temperature: 0° to 60 °C
Storage Temperature: -40° to 60 °C
Operating and Storage Humidity: 0 to 85% max. relative humidity (non-
condensing)
Vibration According to IEC 68-2-6: Operational 5 to 150 Hz, in X, Y, Z
direction for 1.5 hours, 2g's.
Shock According to IEC 68-2-27: Operational 30 g's, 11 msec in 3 directions.
Altitude: Up to 2000 meters
9. CERTIFICATIONS AND COMPLIANCES:
SAFETY
UL Recognized Component, File # E179259, UL61010A-1, CSA C22.2
No. 61010-1
Recognized to U.S. and Canadian requirements under the Component
Recognition Program of Underwriters Laboratories, Inc.
UL Listed, File # E137808, UL508, CSA C22.2 No. 14-M95
LISTED by Und. Lab. Inc. to U.S. and Canadian safety standards
Type 4X Enclosure rating (Face only), UL50
1.0 I
NSTALLI NG THE
Installation
The PAX meets NEMA 4X/IP65 requirements when properly installed. The
unit is intended to be mounted into an enclosed panel. Prepare the panel cutout
to the dimensions shown. Remove the panel latch from the unit. Slide the panel
gasket over the rear of the unit to the back of the bezel. The unit should be
installed fully assembled. Insert the unit into the panel cutout.
BEZEL
LATCHING
SLOTS
PANEL
GASKET
S
ETER
PECI FI CATI ONS
= 3.75 V min.
IH
= 1.9 mA
MAX
M
PANEL
PANEL
LATCH
LATCHING
TABS
PANEL
MOUNTING
SCREWS
IECEE CB Scheme Test Report # 04ME11209-20041018
Issued by Underwriters Laboratories, Inc.
IEC 61010-1, EN 61010-1: Safety requirements for electrical equipment
for measurement, control, and laboratory use, Part 1.
IP65 Enclosure rating (Face only), IEC 529
IP20 Enclosure rating (Rear of unit), IEC 529
ELECTROMAGNETIC COMPATIBILITY
Emissions and Immunity to EN 61326: Electrical Equipment for Measurement,
Control and Laboratory use.
Immunity to Industrial Locations:
Electrostatic discharge
Electromagnetic RF fields
Fast transients (burst)
Surge
RF conducted interference
Power frequency magnetic fields
Voltage dip/interruptions
Emissions:
Emissions
Notes:
1. Criterion A: Normal operation within specified limits.
2. EMI filter placed on the DC power supply, when DC powered: Corcom
#1VB3 or Schaffner #FN610-1/07 (RLC #LFIL0000).
10. CONNECTIONS: High compression cage-clamp terminal block
Wire Strip Length: 0.3" (7.5 mm)
Wire Gage Capacity: 30-14 AWG copper wire.
Torque: 4.5 inch-lbs (0.51 N-m) max.
11. CONSTRUCTION: This unit is rated for NEMA 4X/IP65 outdoor use.
IP20 Touch safe. Installation Category II, Pollution Degree 2. One piece
bezel/case. Flame resistant. Synthetic rubber keypad. Panel gasket and
mounting clip included.
12. WEIGHT: 12 oz (340 g)
ETER
While holding the unit in place, push the panel latch over the rear of the unit
so that the tabs of the panel latch engage in the slots on the case. The panel latch
should be engaged in the farthest forward slot possible. To achieve a proper seal,
tighten the latch screws evenly until the unit is snug in the panel (Torque to
approximately 7 in-lbs [79N-cm]). Do not over-tighten the screws.
Installation Environment
The unit should be installed in a location that does not exceed the maximum
operating temperature and provides good air circulation. Placing the unit near
devices that generate excessive heat should be avoided.
The bezel should be cleaned only with a soft cloth and neutral soap product.
Do NOT use solvents. Continuous exposure to direct sunlight may accelerate the
aging process of the bezel.
Do not use tools of any kind (screwdrivers, pens, pencils, etc.) to operate the
keypad of the unit.
3
EN 61000-4-2
Criterion A
4 kV contact discharge
8 kV air discharge
EN 61000-4-3
Criterion A
10 V/m
EN 61000-4-4
Criterion A
2 kV power
2 kV signal
EN 61000-4-5
Criterion A
1 kV L-L,
2 kV L&N-E power
1 kV signal
EN 61000-4-6
Criterion A
3 V/rms
EN 61000-4-8
Criterion A
30 A/m
EN 61000-4-11
Criterion A
0.5 cycle
EN 55011
Class B
PANEL CUT-OUT
3.62
+.03
-.00
(92
+.8
)
-.0
1.77
+.02
-.00
+.5
(45
)
-.0
2
2

Advertisement

loading