red lion PAX LITE PAXLCR Series Manual

red lion PAX LITE PAXLCR Series Manual

Dual counter and rate meter

Advertisement

MODEL PAXLCR - PAX LITE DUAL COUNTER AND RATE METER
U L
C
US LISTED
R
IND. CONT. EQ.
51EB
For Model No. PAXLCRU0 Only
GENERAL DESCRIPTION
The PAXLCR is a versatile meter that provides a single or dual counter with
rate indication, scaling and dual relay outputs. The 6-digit display has 0.56" high
digits with adjustable display intensity. The display can be toggled manually or
automatically between the selected counter and rate values.
The meter has two signal inputs and a choice of eight different count modes.
These include bi-directional, quadrature and anti-coincidence counting, as well
as a dual counter mode. When programmed as a Dual Counter, each counter has
separate scaling and decimal point selection.
Rate indication is available in all count modes. The Rate Indicator has
separate scaling and decimal point selection, along with programmable display
update times. In addition to the signal inputs, the User Input can be programmed
to perform a variety of meter control functions.
Two setpoint outputs are provided, each with a Form C relay. The outputs can
activate based on either counter or rate setpoint values. An internal batch counter
can be used to count setpoint output activations.
The PAXLCR can be powered from a wide range of AC or DC voltages. The
meter has been specifically designed for harsh industrial environments. With a
NEMA 4X/IP65 sealed bezel and extensive testing to meet CE requirements, the
meter provides a tough yet reliable application solution.
ORDERING INFORMATION
MODEL NO. DESCRIPTION
PAXLCR
Dual Counter & Rate Meter with Dual Relay Output
UL Listed Dual Counter & Rate Meter with Dual
PAXLCRU
Relay Output
DIMENSIONS In inches (mm)
8. 8 . 8 . 8 . 8 . 8
A
B
S 1
P
S 2
P
PAR
SEL
RST
3.80
(96.5)
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
PART NUMBER
PAXLCR00
PAXLCRU0
Note: Recommended minimum clearance (behind the panel) for mounting clip installation is
2.1" (53.4) H x 5.0" (127) W.
1.95
(49.5)
.10
4.10
(2.5)
(104.1)
 6 DIGIT, 0.56" HIGH RED LED DISPLAY
 PROGRAMMABLE SCALING FOR COUNT AND RATE
 BI-DIRECTIONAL COUNTING, UP/DOWN CONTROL
 QUADRATURE SENSING (UP TO 4 TIMES RESOLUTION)
 BUILT-IN BATCH COUNTING CAPABILITY
 PROGRAMMABLE USER INPUT
 DUAL 5 AMP FORM C RELAYS
 UNIVERSALLY POWERED
 NEMA 4X/IP65 SEALED FRONT BEZEL
SAFETY SUMMARY
All safety regulations, local codes and instructions that appear in this and
corresponding literature, or on equipment, must be observed to ensure personal
safety and to prevent damage to either the instrument or equipment connected to
it. If equipment is used in a manner not specified by the manufacturer, the
protection provided by the equipment may be impaired. Do not use this meter
to directly command motors, valves, or other actuators not equipped with
safeguards. To do so can be potentially harmful to persons or equipment in the
event of a fault to the meter
CAUTION: Risk of Danger.
Read complete instructions prior to
installation and operation of the unit.
SPECIFICATIONS
1. DISPLAY: 6 digit, 0.56" (14.2 mm) intensity adjustable Red LED
2. POWER REQUIREMENTS:
AC POWER: 50 to 250 VAC 50/60 Hz, 12 VA
Isolation: 2300 Vrms for 1 min. to all inputs and outputs
DC POWER: 21.6 to 250 VDC, 6 W
DC Out: +24 VDC @ 100 mA if input voltage is greater than 50 VAC/VDC
+24 VDC @ 50 mA if input voltage is less than 50 VDC
3. COUNTER DISPLAYS:
Counter A: 6-digits, enabled in all count modes
Display Designator: "A" to the left side of the display
Display Range: -99999 to 999999
Counter B: 6-digits, enabled in Dual Count mode or Batch Counter
Display Designator: "B" to the left side of the display
Display Range: 0 to 999999 (positive count only)
Overflow Indication: Display "" alternates with overflowed count value
Maximum Count Rates: 50% duty cycle, count mode dependent.
With setpoints disabled: 25 KHz, all modes except Quadrature x4 (23 KHz).
With setpoint(s) enabled: 20 KHz, all modes except Dual Counter (14 KHz),
Quadrature x2 (13 KHz) and Quadrature x4 (12 KHz).
1.75
(44.5)
Bulletin No. PAXLCR- B
Drawing No. LP0749
Released 04/09
CAUTION: Risk of electric shock.
1
2
3
4 5
6 7
8
9
10
11 12
14 15
13
3.60 (91.4)

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the PAX LITE PAXLCR Series and is the answer not in the manual?

Questions and answers

Summary of Contents for red lion PAX LITE PAXLCR Series

  • Page 1 Bulletin No. PAXLCR- B Drawing No. LP0749 Released 04/09 MODEL PAXLCR - PAX LITE DUAL COUNTER AND RATE METER  6 DIGIT, 0.56" HIGH RED LED DISPLAY  PROGRAMMABLE SCALING FOR COUNT AND RATE  BI-DIRECTIONAL COUNTING, UP/DOWN CONTROL  QUADRATURE SENSING (UP TO 4 TIMES RESOLUTION) ...
  • Page 2 4. RATE DISPLAY: 6-digits, may be enabled or disabled in any count mode 11. CONSTRUCTION: This unit is rated for NEMA 4X/IP65 outdoor use. IP20 Display Range: 0 to 999999 Touch safe. Installation Category II, Pollution Degree 2. One piece bezel/ Over Range Display: “”...
  • Page 3: Dip Switches

    2.0 S DIP S ETTING THE WITCHES To access the switches, remove the meter base from the case by firmly FRONT DISPLAY squeezing and pulling back on the side rear finger tabs. This should lower the latch below the case slot (which is located just in front of the finger tabs). It is recommended to release the latch on one side, then start on the other side latch.
  • Page 4: Power Wiring

    3.1 POWER WIRING DC Out Power Power Terminal 3: + 24 VDC OUT + 24V EXC Terminal 1: VAC/DC + AC/DC Terminal 4: Common Terminal 2: VAC/DC - COMMON AC/DC 3.2 INPUT SIGNAL WIRING The meter provides a choice of eight different count modes using two signal inputs, A and B.
  • Page 5: Programming Menu

    4.0 R EVIEWING THE RONT UTTONS AND ISPLAY 8. 8 . 8 . 8 . 8 . 8 BUTTON DISPLAY MODE OPERATION PROGRAMMING MODE OPERATION Access Programming Mode Store selected parameter and index to next parameter Advance through selection list/select digit position in Index display through enabled values parameter value Resets count display(s) and/or outputs...
  • Page 6 5.1 MODULE 1 - I NPUT ETUP ARAMETERS  PARAMETER MENU 1-INP INP Ab A-dPt A-Scf A-rSt A-dir Cnt Ld b-bAt Count Counter A Counter A Counter A Counter A Counter A Counter B Mode Decimal Point Scale Factor Reset Action Count Direction Count Load Batch Count...
  • Page 7 COUNTER B SCALE FACTOR USER INPUT FUNCTION                 The number of input or batch counts is multiplied by the scale factor to MODE DESCRIPTION obtain the desired process value. A scale factor of 1.0000 will result in the DISPLAY display of the actual number of input or batch counts.
  • Page 8 5.2 MODULE 2 - R ETUP ARAMETERS  2-rAtE PARAMETER MENU rt-Enb rt-dPt StYLE rt-dSP rt-INP LO-Udt HI-Udt Rate Rate Decimal Rate Input Rate Scaling Rate Scaling Rate Low Rate High Enable Point Scaling Style Display Value Input Value Update Time Update Time RATE ENABLE RATE LOW UPDATE TIME (DISPLAY UPDATE)
  • Page 9 INPUT FREQUENCY CALCULATION The meter determines the input frequency by summing the number of falling edges received during a sample period of time. The sample period begins on the first falling edge. At this falling edge, the meter starts accumulating time towards Low Update and High Update values.
  • Page 10 FACTORY SERVICE OPERATIONS RESTORE FACTORY DEFAULT SETTINGS            Entering Code 66 will overwrite all user settings with the factory default Select to perform either of the Factory Service Operations shown below. ...
  • Page 11 SETPOINT OUTPUT ACTION SETPOINT STANDBY OPERATION              This parameter selects the action of the Setpoint output as described in the This parameter only applies to Low Acting Boundary Type setpoints. Select chart below.
  • Page 12 PAXLCR PROGRAMMING QUICK OVERVIEW Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com...