Ferroli OMNIA M 3.2 Installation And Owner's Manual page 171

Reversible heat pump units for outdoor installation with dc inverter compressor
Hide thumbs Also See for OMNIA M 3.2:
Table of Contents

Advertisement

Available languages

Available languages

ERROR
MALFUNCTION
CODE
OR PROTECTION
Phase loss or neutral wire and
live wire are connected
reversely(only for three phase
unit)
The condenser outlet
refrigerant temperature sensor
(T3)error.
The ambient temperature
sensor (T4) error.
Suction temperature
sensor(Th) error
Discharge temperature
sensor(Tp) error
Communication fault between
indoor unit and outdoor unit
Communication error between
inverter module PCB A and
main control board PCB B
Three times P6 protect
FAILURE CAUSE
AND CORRECTIVE ACTION
1.Check the power supply cables should be conneted
stable,aviod phase loss.
2.Check whether the sequence of neutral wire and live wire are
connected reversely.
1. The T3 sensor connector is loosen. Reconnect it.
2.The T3 sensor connector is wet or there is water in. remove
the water, make the connector dry. Add waterproof adhesive.
3. The T3 sensor failure, change a new sensor.
1. The T4 sensor connector is loosen. Reconnect it.
2.The T4 sensor connector is wet or there is water in. remove
the water, make the connector dry. Add waterproof adhesive.
3. The T4 sensor failure, change a new sensor.
1. The Th sensor connector is loosen. Re connect it.
2.The Th sensor connector is wet or there is water in. remove
the water, make the connector dry. Add waterproof adhesive.
3. The Th sensor failure, change a new sensor.
1. The Tp sensor connector is loosen. Re connect it.
2.The Tp sensor connector is wet or there is water in. remove
the water, make the connector dry. Add waterproof adhesive
3. The Tp sensor failure, change a new sensor.
1.wire doesn't connect between main control board PCB B and
main control board of indoor unit. connect the wire.
2. Whether there is a high magnetic field or high power
interfere, such as lifts, large power transformers, etc.. To add a
barrier to protect the unit or to move the unit to the other place.
1. Whether there is power connected to the PCB and driven
board. Check the inverter module PCB indicator light is on or
off. If Light is off, reconnect the power supply wire.
2.if light is on, check the wire connection between inverter
module PCB and main control board PCB, if the wire loosen or
broken, reconnect the wire or change a new wire.
3. Replace a new main PCB and driven board in turn.
Same to P6
72

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents