Ferroli OMNIA M 3.2 Installation And Owner's Manual page 169

Reversible heat pump units for outdoor installation with dc inverter compressor
Hide thumbs Also See for OMNIA M 3.2:
Table of Contents

Advertisement

Available languages

Available languages

ERROR
MALFUNCTION
CODE
OR PROTECTION
Solar
temp.sensor(Tsolar) fault
Buffer tank low
temp.sensor(Tbt2) fault
Inlet water temp.sensor
(Tw_in) malfunction
Hydraulic module EEprom
failure
Communication fault between
monobloc
Refrigerant liquid
temp.sensor(T2) fault
Refrigerant gas
temp.sensor(T2B) fault
Room temp.sensor(Ta) fault
Outl et w at er fo r zo ne 2
temp.sensor (Tw2) fault
Outlet water
temp.sensor(Tw_out)
fault
Three times "PP"
protection and
7
"1.Check the resistance of the sensor.
2.The Tsolar sensor connector is loosen,reconnect it.
3.The Tsolar sensor connector is wet or there is water
in,remove the water ,make the connector dry.Add waterproof
adhesive.
4.The Tsolar sensor failure,change a new sensor."
"1.Check the resistance of the sensor.
2.The Tbt12 sensor connector is loosen,reconnect it.
3.The Tbt2 sensor connector is wet or there is water in,remove
the water ,make the connector dry.Add waterproof adhesive.
4.The Tbt2 sensor failure,change a new sensor."
1.Check the resistance of the sensor
2. The Tw_in sensor connector is loosen. Re connect it.
3.The Tw_in sensor connector is wet or there is water in.
remove the water, make the connector dry. Add waterproof
adhesive
4. The Tw_in sensor failure, change a new sensor.
1. The EEprom parameter is error, rewrite the EEprom data.
2. EEprom chip part is broken, change a new EEprom chip
part.
3. main control board of hydraulic module is broken, change a
new PCB.
1.wire doesn't connect between main control board PCB B and
main control board of hydraulic module. connect the wire.
2.Communication wire sequence is not right. Reconnect the
wire in the right sequence.
3. Whether there is a high magnetic field or high power
interfere, such as lifts, large power transformers, etc.. To add a
barrier to protect the unit or to move the unit to the other place.
1.Check the resistance of the sensor
2.The T2 sensor connector is loosen. Re connect it.
3.The T2 sensor connector is wet or there is water in. remove
the water, make the connector dry. Add waterproof adhesive
4. The T2 sensor failure, change a new sensor.
1.Check the resistance of the sensor
2. The T2B sensor connector is loosen. Reconnect it.
3.The T2B sensor connector is wet or there is water in. remove
the water, make the connector dry. Add waterproof adhesive
4. The T2B sensor failure, change a new sensor.
1.Check the resistance of the sensor.
2. The Ta senor is in the interface.
3. The Ta sensor failure
new interface, or reset the Ta, connect a new Ta from the
hydraulic module PCB.
1.Check the resistance of the sensor.
2. The Tw2 sensor connector is loosen. Reconnect it.
3.The Tw2 sensor connector is wet or there is water in.
Remove the water, make the connector dry. add waterproof
adhesive.
4. The Tw2 sensor failure, change a new sensor.
1. The TW_out sensor connector is loosen. Reconnect it.
2.The TW_out sensor connector is wet or there is water in.
remove the water, make the connector dry. add waterproof
adhesive.
3. The TW_out sensor failure, change a new sensor.
The same to "PP".
Tw_out
70
FAILURE CAUSE
AND CORRECTIVE ACTION
change a new sensor or change a

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents