ABB ACS180 Firmware Manual page 265

Machinery control program
Hide thumbs Also See for ACS180:
Table of Contents

Advertisement

No.
Name/Value
58.04
Baud rate
Autodetect
4.8 kbps
9.6 kbps
19.2 kbps
38.4 kbps
57.6 kbps
76.8 kbps
115.2 kbps
58.05
Parity
8 NONE 1
8 NONE 2
8 EVEN 1
8 ODD 1
58.06
Communication
control
Enabled
Refresh settings
Silent mode
Description
Selects the transfer rate of the fieldbus link.
When using selection Autodetect, the parity setting of the
bus must be known and configured in parameter
Parity. When parameter
Autodetect, the EFB settings must be refreshed with
parameter 58.06. The bus is monitored for a period of time
and the detected baud rate is set as the value of this
parameter.
Changes to this parameter take effect after the control unit
is rebooted or the new settings validated by parameter
58.06 Communication control (Refresh
Baud rate detected automatically.
4.8 kbit/s.
9.6 kbit/s.
19.2 kbit/s.
38.4 kbit/s.
57.6 kbit/s.
76.8 kbit/s.
115.2 kbit/s.
Selects the type of parity bit and number of stop bits.
Changes to this parameter take effect after the control unit
is rebooted or the new settings validated by parameter
58.06 Communication control (Refresh
Eight data bits, no parity bit, one stop bit.
Eight data bits, no parity bit, two stop bits.
Eight data bits, even parity bit, one stop bit.
Eight data bits, odd parity bit, one stop bit.
Takes changed EFB settings in use, or activates silent
mode.
Normal operation.
Refreshes settings (Modbus parameters 58.01...58.05,
58.14...58.17, 58.25, 58.28...58.34) and takes changed
EFB configuration settings in use.
Reverts automatically to Enabled.
Activates silent mode (no messages are transmitted).
Silent mode can be terminated by activating the
settings
selection of this parameter.
58.04 Baud rate
is set to
settings).
settings).
Parameters 265
Default
FbEq 16
19.2 kbps
58.05
0
1
2
3
4
5
6
7
8 EVEN 1
0
1
2
3
Enabled
0
1
2
Refresh

Advertisement

Table of Contents
loading

Table of Contents