158 Parameters
No.
Name/Value
Flying start
Flying start+boost
21.21
DC hold frequency
0.00...1000.00 Hz
21.22
Start delay
0.00...60.00 s
21.23
Smooth start
Disabled
Enabled always
Start only
21.24
Smooth start current
10.0... 100.0%
21.25
Smooth start speed
2.0... 100.0%
Description
The drive automatically selects the correct output
frequency to start a rotating motor. If the motor is already
rotating, drive will start smoothly at the current frequency.
The mode will start the motor with vector control and
switch to scalar control on the fly when the motor speed
has been found. Compared to the Automatic start mode,
Flying start detects the motor speed faster. Flying start
requires more accurate information about motor model.
Therefore standstill ID run is done automatically when the
drive is started for the first time after selecting Flying start.
Motor plate values should be accurate. Wrong plate
values may decrease the starting performance.
Note: Flying start cannot be used in multimotor systems.
Note: During flying start, the drive will at first run in vector
control mode. This is why, when using flying start, the
drive nominal current setting must be in the allowed range
for vector control mode. See parameter 99.06.
Flying start with torque boost.
Flying start is performed first and the motor is magnetized.
If the speed is found to be zero, torque boost is applied.
Defines the DC hold frequency, which is used instead of
parameter
21.09 DC hold speed
in use is Scalar frequency mode. See parameters
Actual operation
mode,
section
DC hold
on page 66.
DC hold frequency.
Defines the start delay. After the conditions for start have
been fulfilled, the drive waits until the delay has elapsed
and then starts the motor. During the delay, warning
Start delay
is shown.
Start delay can be used with all start modes.
Start delay
Enables smooth start function. Smooth start function
restricts the motor current below the limit defined by
parameter
21.24 Smooth start current
speed is below
21.25 Smooth start
Warning: Long run operation of smooth start at low
speed with high current may heat the motor.
Smooth start disabled
Smooth start function is always active when speed is
below limit.
Smooth start function is only active after start while the
speed is below limit.
Current applied to motor when the smooth start is active.
Value in percent of the motor nominal current.
Set the smooth start speed when the current is applied.
Value in percent of the motor nominal speed.
when the operating mode
21.08 DC current
control, and
when the motor
speed.
Default
FbEq 16
5
6
5.00 Hz
19.01
1 = 1 Hz
0.00 s
AFE9
1 = 1 s
Disabled
0
1
2
50.0%
1=1%
10.0%
1=1%