256 Parameters
No.
Name/Value
45.19
Comparison power
0.00...100000.00 kW
45.21
Energy calculations
reset
Done
Reset
45.24
Hourly peak power
value
-3000.00 ... 3000.00
kW
45.25
Hourly peak power
time
45.26
Hourly total energy
(resettable)
-3000.00 ... 3000.00
kWh
45.27
Daily peak power
value (resettable)
-3000.00 ... 3000.00
kW
45.28
Daily peak power time
45.29
Daily total energy
(resettable)
-30000.00 ...
30000.00 kWh
45.30
Last day total energy
-30000.00 ...
30000.00 kWh
Description
Actual power that the motor absorbs when connected
direct-on-line and operating the application. The value is
used for reference when energy savings are calculated.
Note: The accuracy of the energy savings calculation is
directly dependent on the accuracy of this value. If nothing
is entered here, then the nominal motor power is used by
the calculation, but that may inflate the energy savings
reported as many motors do not absorb nameplate power.
Motor power.
Resets the savings counter parameters 45.01...45.10.
Reset not requested (normal operation), or reset
complete.
Reset the savings counter parameters. The value reverts
automatically to Done.
Value of the peak power during the last hour, that is, the
most recent 60 minutes after the drive has been powered
up.
The parameter is updated once every 10 minutes unless
the hourly peak is found in the most recent 10 minutes. In
that case, the values is shown immediately.
Peak power value.
Time of the peak power value during the last hour.
Time.
Total energy consumption during the last hour, that is, the
most recent 60 minutes.
You can reset the value by setting it to zero.
Total energy.
Value of the peak power since midnight of the present
day.
You can reset the value by setting it to zero.
Peak power value.
Time of the peak power since midnight of the present day. 00:00:00
Time.
Total energy consumption since midnight of the present
day.
You can reset the value by setting it to zero.
Total energy.
Total energy consumption during the previous day, that is,
between midnight of the previous day and midnight of the
present day
Total energy.
Default
FbEq 16
0.00 kW
1 = 1 kW
Done
0
1
0.00 kW
10 = 1 kW
00:00:00
N/A
0.00 kWh
10 = 1 kWh
0.00 kW
10 = 1 kW
N/A
0.00 kWh
1 = 1 kWh
0.00 kWh
1 = 1 kWh