4.6 Mount the burner on the boiler

1.
Separate the burner body and the fl ange.
2.
Remove the brake disc from the oil pipe.
3.
Install the selected nozzle. (See Technical data)
4.
Install the brake disc on the oil pipe
5.
Remove the burner pipe from the fl ange.
6.
Install the fl ange with gasket on the boiler.
7.
Install the burner pipe on the fl ange. Make sure that the holes in the
front edge of the burner pipe are pointing down (not on all burner
pipes). This allows any drops of oil to run out.
8.
Insulate between the burner and boiler door to reduce radiated heat.
9.
Install the burner body on the fl ange.
10.
Lock the burner body using with the nut/nuts.
11.
Connect the oil pipes to the pump, refer to the chapter - servicing of
burners.
12.
Connect the burner electrically, refer to the chapter - servicing of
burners.
!
If the burner tube must be installed from the inside
of the boiler, this means that the boiler must be
opened or have a spectacle fl ange that is desig-
ned so that it can be reconnected with the burner
tube mounted.

4.7 Check oil line seals

Once the burner has been installed and commissioned, the seals of the
various coupling elements should be checked.
When a leak is detected, it is usually suffi cient to tighten the coupling
element that is leaking.