Mount The Burner On The Boiler; Check Oil Line Seals - Bentone B 40 A2.2H Installation And Maintenance Instruction

Hide thumbs Also See for B 40 A2.2H:
Table of Contents

Advertisement

4.6 Mount the burner on the boiler

1.
Separate the burner body and the flange.
2.
Remove the brake disc from the oil pipe.
3.
Install the selected nozzle. (See Technical data)
4.
Install the brake disc on the oil pipe
5.
Remove the burner pipe from the flange.
6.
Install the flange with gasket on the boiler.
7.
Install the burner pipe on the flange. Make sure that the holes in the
front edge of the burner pipe are pointing down (not on all burner
pipes). This allows any drops of oil to run out.
8.
Insulate between the burner and boiler door to reduce radiated
heat.
9.
Install the burner body on the flange.
10.
Lock the burner body using with the nut/nuts.
11.
Connect the oil pipes to the pump, refer to the chapter - servicing
of burners
12.
Connect the burner electrically, refer to the chapter - servicing of
burners

4.7 Check oil line seals

Once the burner has been installed and commissioned, the seals of the
various coupling elements should be checked (A).
When a leak is detected, it is usually sufficient to tighten the coupling
element that is leaking.
A
16
Bentone
A
A
A
165 105 45

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents