7Ts720 Command Output Module; Peripheral Module Housing - Siemens SIPROTEC 7SS60 Manual

Centralized numerical busbar protection
Table of Contents

Advertisement

9.1.2.3

7TS720 command output module

Auxiliary voltage
Power
consumption
Command contacts
Weight
9.1.3

Peripheral module housing

Design
7SS60 Manual
E50417–G1176–C132–A2
Rated auxiliary voltageU
(permissible voltage range)
Rated auxiliary voltage
48 V
60 V
110 V
125 V
220 V
250 V
Number of relays
Contacts per relay
for short-term operation < 10 s
Pickup time
Switching capacity
MAKE
BREAK
Switching voltage
permissible current
continuous
0.5 s
1)
limited by the continuous power dissipation of the device
Housing
Dimensions
Weight
Degree of protection according
to IEC 60529-1
for the device
for operator protection
48/60 Vdc
H
110/125 Vdc
220/250 Vdc
settable, see Figure A-8
as delivered: 220/250 Vdc
max. power consumption, continuous
0.7 W
1.0 W
1.9 W
2.4 W
3.1 W
3.9 W
8
2 NO contacts
1)
approx. 7 ms
1000 W/VA
30 W/VA
250 V ac/dc
5 A
30 A
approx. 0.5 kg
7XP204
see Figure 9-2
approx. 3.5 kg
IP 51 (front)
IP 20 (rear)
IP 2X (if all connectors and blanking plates
are fitted)
Technical Data
(38 to 72 Vdc)
(88 to 150 Vdc)
(176 to 300 Vdc)
1
/
19"
2
9-7

Advertisement

Table of Contents
loading

Table of Contents