Marshalling Of The Command Relays - Block 64 - Siemens SIPROTEC 7SD600 System Manual

Numerical line differential protection
Hide thumbs Also See for SIPROTEC 7SD600:
Table of Contents

Advertisement

5
Preparation instructions
Numerical line differential protection SIPROTEC 7SD600 V3.0
5.5.5
Marshalling of the command relays -
block 64
The device has 2 command relays with trip duty, desi
gnated as CR 1 and CR 2. They can be marshalled in
block 64. You can reach the block from the initial state
of the device in level 1 as follows: Press the B key
(forwards), switch to the 2nd operating level with the
" key (next level), scroll with the B key until block
60 appears on the display. Switch to operating level 3
with the " key and scroll to block 64 with the B key
!: Marshalling command relay. Selection is carried
out as described in section 5.5.1. Multiple commands
are permitted, i.e. a logical indication can be transmit
ted to several command relays (see section 5.5.1).
A
6 4
R O U T
B
C R
Use the " key to go to the first command relay:
A
6 4
R
O U T
B
C R 1
Switch to the selection level with the " key:
6 4
C R 1
1
A
D e v. gen. Tr.
6 4
C R 1
2
A
not a l l.
5 - 28
System manual
Order no. E50417-G1176-C069-A1
All indications shown in table 5.3 can be marshalled
to command relays. Command functions have no ef
fect if the relevant protective function in the device is
not available, switched off or has been configured so
that it is not available or is parameterized as indication
only.
The general diagrams in appendix A show the assign
ment of the command relays on delivery. The follo
wing boxes show some examples for command
relay 1.
Table 5.6 shows all factory settings.
If several protective functions are to trip the same
circuit breaker, the relevant command relay must be
activated by the relevant command function.
[6400]
Beginning of the block
"
"Marshalling of command relays"
[6401]
Marshalling for command relay 1
"
[6402]
Command relay 1 is factory set as follows:
B
1. Protection (gen.) general trip; Fno. 511.
[6403]
Y
2. No further command functions for command relay
B
Siemens AG January 1999