Peripheral Modules; 7Tm700 Restraint/Command Output Module - Siemens SIPROTEC 7SS60 Manual

Centralized numerical busbar protection
Table of Contents

Advertisement

9.1.2

Peripheral modules

9.1.2.1

7TM700 restraint/command output module

Measuring input I
s
Auxiliary voltage
Power
consumption
Command contacts
Weight
7SS60 Manual
E50417–G1176–C132–A2
Number of restraint units
Rated current
Rated frequency
Dynamic overload capability
(pulse current)
Thermal overload capability (rms)
(where external summation or matching
current transformers are used,
their limit data must be observed)
Rated auxiliary voltage U
(permitted voltage range)
Rated auxiliary voltage
48 V
60 V
110 V
125 V
220 V
250 V
Number of relays
Contacts per relay
for short-term operation < 10 s
Pickup time
Switching capacity
MAKE
BREAK
Switching voltage
Permissible currents
continuous
0.5 s
1)
limited by the continuous power dissipation of the device
5
100 mA
16.7Hz, 50 Hz, 60 Hz
250 x I
100 x I
30 x I
4 x I
48/60 Vdc
H
110/125 Vdc
220/250 Vdc
settable, see Figure A-5
As delivered: 220/250 Vdc
max. power consumption, continuous
0.7 W
1.0 W
1.9 W
2.4 W
3.1 W
3.9 W
5
2 NO contacts
1)
approx. 7 ms
1000 W/VA
30 W/VA
250 V ac/dc
5 A
30 A
approx. 2.0 kg
Technical Data
one half cycle
N
for ≤ 1 s
N
for ≤ 10 s
N
continuous
N
(38 to 72 Vdc)
(88 to 150 Vdc)
(176 to 300 Vdc)
9-5