Marshalling Of The Led Indicators - Siemens SIPROTEC 7SS60 Manual

Centralized numerical busbar protection
Table of Contents

Advertisement

4.2.3.4

Marshalling of the LED indicators

Block 63
7SS60 Manual
E50417-G1176-C132-A2
The unit contains 6 LEDs for optical indications, 4 of which can be marshalled. They
are designated LED 1 to LED 4 and can be marshalled in address block . The block
is reached from the initial display in level 1 as follows: press the key
move to the 2nd operation level by key
until block  appears in the display. Key
block  0$56+ /(' ,1'
The selection procedure is carried out as described in Subsection 4.2.3.1.
Multiple allocation is possible, i.e a logical signal can be marshalled to more than one
LED (refer to Subsection 4.2.3.1).
Apart from the logical functions, each LED can be marshalled to operate either in the
memorized mode or non-memorized mode. Each annunciation function is displayed
with the index "0µ ("0µ = memorized).
The marshallable annunciation functions are the same as those listed in Table 4-4.
Table 4-6 shows all LED indicators as they are preset from the factory.
The selected function must be confirmed by the enter key E.
Following password input, all marshallable output functions can be scrolled through on
the display by repeated use of the key +. Backscrolling in the offered suggestions is
possible with the key –. When the required function appears, press the enter key E.
After this, further functions can be allocated to LED 1 (with further index numbers 1 to
20) by using the key
selection place is to be assigned to physical unit, selection is made with the function
QRW DOO (not allocated).
Leave the selection level for LED 1 with key
arrow key
.
Table 4-6
Presettings of LED indicators
4th level
MARSHALLING
63 MARSH LED 1
63 MARSH LED 2
63 MARSH LED 3
63 MARSH LED 4
(next level); press the key
leads to operation level 3 with address
. Each selection must be confirmed by pressing the key E. If a
5th level
FNo.
LEDs
6 3 L E D 1 1
7914
B P T r i p
6 3 L E D 2 1
7921
I d s f l t
6 3 L E D 3 1
7910
B P b l k
6 3 L E D 4 1
1
n o t
a l l .
. You can then go to the LED with the
Remark
Block heading
Busbar protection: Trip
IDIFF supervision:
Fault detected
Busbar protection blocked
not allocated
Configuration
(forwards),
repeatedly
4-11