Hints On Setting; Overview Of Parameters; Annunciations - Siemens SIPROTEC 7SS60 Manual

Centralized numerical busbar protection
Table of Contents

Advertisement

5.3.2

Hints on setting

Rated system
frequency
Lockout function
5.3.3

Overview of parameters

DIGSI
Parameter
addr.
1101
01 FREQ
1134
01 T-TRP
1135
01 L.Out
5.3.4

Annunciations

FNo.
Text on LC display
7721
LockOut
7SS60 Manual
E50417-G1176-C132-A2
The default setting is  +]; it needs to be changed only for a system frequency of
 +].
16.7 Hz are available in a version with separate order no.
Note:
The parameter  )5(4 () can only be called up in versions for 50 Hz or 60 Hz.
In systems with a rated frequency of 16.7 Hz, the parameter  )5(4 () is not
displayed at all.
If the Lockout function is set to 21, the lockout state can only be reset via a binary
input. If 21EXWW is set, the lockout can be reset with the N key or with a binary input.
Possible settings
50 Hz
60 Hz
0.01 s to 32.00 s
OFF
ON
ON/key
Lockout state
Default setting
50 Hz
Rated frequency of power system
0.15 s
Minimum duration of TRIP command
OFF
Lockout function
Logical functions
Functions
Explanation
5-15

Advertisement

Table of Contents
loading

Table of Contents