Download Print this page
Penn P216 Product Bulletin

Penn P216 Product Bulletin

Condenser fan speed controller

Advertisement

Quick Links

PB_P216_11 2016
P216
Condenser fan speed controller
Product bulletin
These controllers are designed for speed variation of single
phase motors, especially for fan speed control on air cooled
condensers. Head pressure control of a refrigeration system,
through speed variation of the fan on an air-cooled condenser,
results in optimum performance throughout the year.
Using a pressure transducer as the input device to the fan
speed controller, gives the most direct and fastest response
to pressure variations in the refrigerant system. The controller
varies the supply voltage to the motor from 20% to 100%
over the proportional band using the phase cutting principle.
If the pressure drops below the adjusted setpoint minus the
proportional band, the output to the motor is zero volt or the
adjusted min. speed setting. This provides speed variation of
permanent split capacitor or shaded pole motors which do not
draw more than 12 A (rms) full load current.
The controller used for dual pressure input varies the fan speed
by directly sensing the pressure changes of two separate
refrigerant circuits. The setpoint of each pressure transducer
can be separately adjusted. The controller selects the input with
the greatest cooling demand to control the fan speed.
The transducers can be used in non-corrosive refrigerant
systems.
The motor manufacturer should have approved his product for
this speed control principle. It is recommended to confirm with
the electric motor manufacturer, that the motor can be used
with a controller, using the phase cutting principle for speed
variation.
You can also provide a copy of this P216 product data sheet to
the motor manufacturer/supplier for review.
Features
• The new benchmark in standard FSC
• Easy to install and easy to operate
• Output range: 0,5 to 12 Amp (1 phase)
• Input 0-10 Vdc
• Including 0-50 bar pressure transducer P499VCS-405C
• Heatpump mode
• Reverse operation mode
• Master / Slave mode
• Fixed pressure ranges for direct replacement (P215)
• Setpoint and min speed potmeters

Advertisement

loading

Summary of Contents for Penn P216

  • Page 1 You can also provide a copy of this P216 product data sheet to the motor manufacturer/supplier for review. Features •...
  • Page 2: Dimensions (Mm)

    Dimensions (mm) Installation The P216 can be used for single or dual pressure input. In the case of dual input the controller selects the input with the greater cooling demand to control the fan speed. There are four pressure ranges: •...
  • Page 3 Setpoint Series controller before finishing wiring and checking all wiring connections. Short circuits or improperly connected wires can result in damage to the P216 series controller and void any warranty. IMPORTANT: Do not exceed the P216 Series Fan Speed HP C REV Controller electrical ratings.
  • Page 4 Motor never stops, always runs at min speed or greater, depending on conditions. OFF = Minimum speed feature is disabled. Motor shuts completely off at low pressure P216 operation using P499VCS-405C transducers Setpoint range CCW - CW Proportional band Mode...
  • Page 5 PB_P216_11 2016 Normal operation example using a 230 V supply Output voltage vs input pressure DIP switch block Min speed 20% 100% Setpoint 60% from “-” 220 V Note Set switches 1–3 as shown to select a 14-24 Bar setpoint range with a 4 Bar proportional band.
  • Page 6 %DI = 55 means that a 5A motor consumes a 2,75 A more current so 7,75 A at inrush and up to medium speed. This means that the P216 is limited to 7,75 A, so it is not possible to connect 2 motors in parallel.
  • Page 7: Technical Specification

    PB_P216_11 2016 Technical specification Product type P216EEA-2K / P216EEA-101C Power supply 208 - 240 VAC, 50/60 Hz Pressure range Adjustable 4 to 10 bar setpoint, prop band fixed at 2.0 bar Adjustable 8 to 14 bar setpoint, prop band fixed at 2.5 bar Adjustable 14 to 24 bar setpoint, prop band fixed at 4.0 bar Adjustable 22 to 42 bar setpoint, prop band fixed at 5.0 bar Pressure transducer...