P70, P72, and P170 Series Controls for Low
Pressure Applications
Installation Instructions
Applications
P70, P72, and P170 Series Controls for Low Pressure
Applications provide low-side pressure control on
commercial refrigeration and air-conditioning
applications.
IMPORTANT: Use this P70, P72, or P170 Series
Control for Low Pressure Applications only as an
operating control. Where failure or malfunction of the
P70, P72, or P170 Series Control could lead to
personal injury or property damage to the controlled
equipment or other property, additional precautions
must be designed into the control system.
Incorporate and maintain other devices, such as
supervisory or alarm systems or safety or limit
controls, intended to warn of or protect against
failure or malfunction of the P70, P72, or P170
Series Control.
P70A and P170A type models with Single-Pole Single-
Throw (SPST) Open-Low switch action are the most
popular models and are typically used for Open-Low
operation and pump-down control. See Table 1 through
Table 4.
P70 and P170 Series control models are also available
with SPST Open-High switch action and are typically
used for capacity control. See Table 3 and Table 4.
Control models with Single-Pole Double-Throw (SPDT)
or 4-wire, 2-circuit switch action allow users to install
alarm devices or other control circuits. See Table 4.
Table 1: Standard P70, P72 and P170 MICRO-SET® Control Models for Low Pressure Applications (for
Non-corrosive Refrigerants)
Model
Switch Action
Number
P70AB-12
SPST
Open-Low
P170AB-12
Refer to the
Range
in. Hg to psig
(kPa)
12 in. Hg to 80 psig
(-41 to 551 kPa)
P70, P72, and P170 Series Controls for Low Pressure Applications Installation
QuickLIT Web site
for the most up-to-date version of this document.
P72 Series control models have a Double-Pole Single-
Throw (DPST) switch with load-carrying contacts that
provide direct control of 208/240 VAC single-phase
motors up to 3 hp, 480 VAC single-phase,
non-compressor motors, and 208/220 VAC 3-phase
motors up to 5 hp. See Table 4.
These controls are available in several pressure
ranges and are compatible with most common
refrigerants. They may also be used on air, water,
and other non-corrosive fluid applications.
Ammonia-compatible models are also available. See
Table 3.
The MICRO-SET® option provides fine adjustment of
the differential setting for precision pressure control of
critical low pressure applications.
Some models feature Limited Knob Adjustment, which
restricts adjustment of the pressure settings and deters
overadjustment or tampering. See Limited Knob
Adjustment.
The Manual Reset Lockout mechanism does not allow
the control to automatically reset after the control has
Cutout, providing shutdown capability for unmonitored
equipment. See Manual Reset Operation.
NEMA 1 enclosures are standard on most models.
NEMA 3R enclosures are available on select models.
Table 1 through Table 4 list the standard models and
features of P70, P72, and P170 controls for low
pressure applications. These standard models are
available through most authorized
Johnson Controls/PENN® distributors.
Differential
Pressure
psi (kPa)
Connection
Minimum 5 (34)
36 in. Cap. with
Maximum 35 (241)
1/4 in. Flare Nut
1/4 in. Male Flare
Connector
Part No. 24-7664-1601, Rev. G
Issued March 2016
Maximum
Overpressure
psig (kPa)
325
(2,241)
Instructions
1

Advertisement

Table of Contents
loading

Summary of Contents for Penn P70 Series

  • Page 1 See Table 4. pressure applications. These standard models are available through most authorized Johnson Controls/PENN® distributors. Table 1: Standard P70, P72 and P170 MICRO-SET® Control Models for Low Pressure Applications (for Non-corrosive Refrigerants) Model...
  • Page 2 Table 2: Standard P70, P72 and P170 Control Models for Low Pressure Applications (For High Pressure Non-Corrosive Refrigerants) Model Switch Action Range Differential Pressure Maximum Number in. Hg to psig psi (kPa) Connection Overpressure (kPa) psig (kPa) P70AA-2 SPST 0 to 150 psig Adjustable 36 in.
  • Page 3: Installation

    Installation Mounting Dimensions CAUTION: Risk of Property Damage. See Figure 1 and Figure 2 for dimensional information. Mount the pressure control separately These dimensions are nominal and are subject to from the electrical cabinet and seal all accepted manufacturing tolerances and application electrical piping to prevent ammonia from variables.
  • Page 4 • Use the two inner holes with the Universal P70, P72, and P170 controls for low pressure Mounting Bracket (and screws supplied) when applications are available with several switch options mounting the control to a flat horizontal and electrical ratings. Check the label inside the control surface.
  • Page 5 Figure 7: Typical Wiring for DPST Switch Figure 6: Typical Wiring for 4-Wire, 2-Circuit (P72A and B Type Models) Switch (P70G and H Type Models) Table 5: Single Pressure Controls Switch Action, Low Events, High Events, Model Types, and Electrical Rating Table References Switch and Action Low Event...
  • Page 6: Setup And Adjustments

    Piping Setup and Adjustments CAUTION: Risk of Environmental and CAUTION: Risk of Property Damage. Property Damage. Obtain and use the compressor Avoid sharp bends in the capillary tubes. manufacturer’s net oil bearing pressure Sharp bends can weaken or kink capillary specifications.
  • Page 7 Figure 8: Adjusting P70, P72, and P170 Controls for Low Pressure Applications Limited Knob Adjustment 3. Place the indicator plate, as shown in Figure 9, to lock either the range screw or differential screw in Some models are supplied with a Limited Knob the desired setting.
  • Page 8 Checkout Procedure for Low Pressure Cut-out 3. Slowly front seat the suction valve and allow the low side to pump down. Observe the control’s low Controls event switching pressure on the gauge. IMPORTANT: Use the pressure control settings 4. Slowly back the suction valve off the front-seated recommended by the manufacturer of the controlled position and allow the low side pressure to rise.
  • Page 9: Technical Specifications

    Technical Specifications Table 6: SPST Electrical Ratings (P70A, B, C, D, and P170A, B, C, D Type Models) Standard Single-Phase Ratings Hermetic Compressor Single-Phase Ratings 208/240 VAC 600 VAC Motor Full-Load Amperes 18.7 Motor Locked-Rotor Amperes 112.2 28.8 Non-Inductive Amperes Pilot Duty 125 VA at 120–600 VAC;...
  • Page 10 Building Efficiency 507 E. Michigan Street, Milwaukee, WI 53202 ® Johnson Controls and PENN are registered trademarks of Johnson Controls, Inc. in the United States of America and/or other countries. All other trademarks used herein are the property of their respective owners. © Copyright 2016 by Johnson Controls, Inc. All rights reserved.
  • Page 11: Instrucciones De Instalación

    Controles para Aplicaciones de Baja Presión Series P70, P72, y P170 Part No. 24-7664-1601, Rev. G Instrucciones de Instalación Publicado Marzo de 2016 Consulte el sitio web de QuickLIT para obtener la versión más reciente de este documento. Aplicación Los modelos de la Serie P72 tienen un interruptor de Dos Polos-Un Tiro (DPST) con contactos para llevar la Los Controles para Aplicaciones de Baja Presión de carga que proporcionan control directo a motores...
  • Page 12 Tabla 2: Modelos Estándar de Control P70, P72 y P170 para Aplicaciones de Baja Presión (para Refrigerantes de Alta Presión No Corrosivos) Número Acción del Rango Diferencial Conexión de Presión Máxima del Modelo Interruptor pulg. Hg a psig psi (kPa) Sobrepresión (kPa) psig (kPa)
  • Page 13: Instalación

    Instalación Montaje Dimensiones PRECAUCIÓN: Riesgo de Daño al Vea las Figura 1 y Figura 2 para información sobre Equipo. El control de presión se debe dimensiones. instalar separadamente del gabinete eléctrico y se deben sellar todos los Nota: Estas dimensiones son nominales y están sujetas a conductos eléctricos para evitar que el las tolerancias de manufactura y variables de la aplicación amoníaco se filtre a los componentes...
  • Page 14: Instalación Eléctrica

    • Use dos tornillos o pernos a través de los dos Instalación Eléctrica orificios exteriores en el reverso de la caja de ADVERTENCIA: Riesgo de descarga control cuando instale el control directamente Eléctrica. Desconecte la corriente eléctrica en una superficie vertical plana. Ver Figura 3. antes de iniciar las conexiones eléctricas para •...
  • Page 15 Corriente Alarma Circuito Alarma de Alarma Carga Línea Carga Línea Circuito principal (Línea a M2) se abre 1 a 3 se abre, y 1 a 2 se cierra y el circuito auxiliar (Línea a M1) se al incrementar la presión. cierra al incrementar la presión Figura 6: Alambrado Típico para Interruptor de Figura 5: Alambrado Típico para Interruptor...
  • Page 16 Conexiones de Presión Ajustes PRECAUCIÓN: Riesgo de daños al PRECAUCIÓN: Riesgo de daños a la medio ambiente y a la propiedad propiedad. Evite cualquier doblez agudo en los tubos Obtenga y utilice la especificación del capilares. Dobleces agudos pueden debilitar fabricante del compresor de la presión neta o plegar los tubos capilares, lo que resultaría de aceite de lubricación.
  • Page 17 Figura 8: Ajuste de los Controles P70, P72 y P170 para Aplicaciones de Baja Presión Ajuste de los Controles MICRO-SET® Para instalar el Juego de Herramientas para el Ajuste de Perilla Limitado: Los controles de presión de lado de baja MICRO- SET®...
  • Page 18 4. Instale la perilla en el otro tornillo de ajuste, y 2. Agregue un medidor de presión confiable al puerto apriete el tornillo de ajuste. Un tope en el fondo de de servicio de la línea de succión y permita que el la perilla limita el ajuste del tornillo a menos de una sistema trabaje en condiciones normales.
  • Page 19 Clasificaciones Eléctricas Tabla 6: Clasificaciones Eléctricas del Interruptor SPST (Tipos P70A, B, C, D, y P170A, B, C, D) Clasificaciones de Motores Monofásicos Clasificaciones para Estándares Compresor Hermético Monofásico 120 VCA 208 VCA 240 VCA *480 *600 208/240 VCA Amperios del Motor con 18.7 Carga Completa Amperios del Motor con el...
  • Page 20 CHINA Building Efficiency 507 E. Michigan Street, Milwaukee, WI 53202 PENN ® y Johnson Controls ® son marcas registradas de Johnson Controls, Inc. Todas las demás marcas aquí mencionadas son marcas de sus respectivos propietarios. © 2016 Johnson Controls, Inc.

Table of Contents