Download Print this page
Penn TC3224N9R Installation Manual

Penn TC3224N9R Installation Manual

Controller for refrigerated cabinets, counters and islands, with energy-saving strategies

Advertisement

Quick Links

PENN | TC3224N9R | Installation Guide Rev. B | Part No. 24-7664-03531 | Page 1 of 3 | 07 April 2020
TC3224N9R
E
ENGLISH
-
Controller for low temperature units.
-
Universal power supply 115... 230 VAC.
-
Incorporated clock.
-
Cabinet probe and evaporator probe (NTC, 10,000 ohm at 77 °F).
-
Door switch input.
-
Alarm buzzer.
-
RS-485 MODBUS subordinate port for BMS.
-
Cooling or heating operation.
1
MEASUREMENTS AND INSTALLATION
Measurements in mm (inches). To be fitted to a panel, snap-in brackets provided.
INSTALLATION PRECAUTIONS
-
The thickness of the panel must be between 0.8 and 2.0 mm (1/32 and 1/16 in)
-
Ensure that the working conditions are within the limits stated in the TECHNICAL
SPECIFICATIONS section.
-
Do not install the device close to heat sources, equipment with a strong magnetic field,
in places subject to direct sunlight, rain, damp, excessive dust, mechanical vibrations
or shocks.
-
In compliance with safety regulations, the device must be installed properly to ensure
adequate protection from contact with electrical parts. All protective parts must be
fixed in such a way as to need the aid of a tool to remove them.
2
ELECTRICAL CONNECTION
Important
- Use cables of an adequate wire gauge for the current running through them.
- To reduce any electromagnetic interference connect the power cables as far away
as possible from the signal cables.
-
Power supply for TC3224N9R: 115... 230 VAC.
PRECAUTIONS FOR ELECTRICAL CONNECTION
If you use an electrical or pneumatic screwdriver, adjust the torque to a maximum of
-
0.5 N•m (4 in. lb).
If the device was moved from a cold to a warm place, the humidity may have caused
-
condensation to form inside. Wait about an hour before switching on the power.
Make sure that the supply voltage, electrical frequency and power are within the set
-
limits. See the section TECHNICAL SPECIFICATIONS.
Disconnect the power supply before doing any type of maintenance.
-
-
Do not use the device as safety device.
For repairs and for further information, contact the PENN sales network.
-
3
FIRST-TIME
1.
Install following the instructions given in the section MEASUREMENTS AND INSTALLA-
TION.
2.
Power up the device as shown in the section ELECTRICAL CONNECTION and an internal
test will be run.
The test normally takes a few seconds, when it is finished the display will switch off.
3.
Configure the device as shown in Table 6.1 in the section SETTINGS.
Recommended configuration parameters for first-time use.
PAR.
DEF.
PARAMETER
SP
0.0
setpoint
P2
0
temperature unit of measurement
d1
0
defrost type
Then check that the remaining settings are appropriate; see the section CONFIGURA-
TION PARAMETERS.
4.
Disconnect the device from the mains.
5.
Make the electrical connection as shown in the section ELECTRICAL CONNECTION with-
out powering up the device.
6.
Power up the device.
4
USER INTERFACE AND MAIN FUNCTIONS
4.1
Switching the device on/off
1.
If POF = 1, touch the ON/STAND-BY key for 4 s.
If the device is switched on, the display will show the P5 value ("cabinet temperature" default);
if the display shows an alarm code, see the section ALARMS.
Controller for refrigerated cabinets, counters and islands,
LED
ON
compressor on
defrost or pre-dripping
active
evaporator fan on
saved HACCP alarm
HACCP
energy saving active
request for compres-
sor service
view temperature
°C/°F
auxiliary load on
AUX
device off
If 30 s have elapsed without the keys being pressed, the display will show the "Loc" label and
the keypad will lock automatically.
4.2
Unlock keypad
Touch any key for 1 s: the display will show the label "UnL".
4.3
Set the setpoint
Check that the keypad is not locked.
1.
2.
3.
4.4
Activate manual defrost (if r5 = 0, default)
Check that the keypad is not locked and that overcooling is not active.
1.
If P3 = 1 (default), defrost is activated provided that the evaporator temperature is lower than
the d2 threshold.
4.5
Cabinet light on/off (if u1 = 0, default)
1.
-
if u1 = 1, the anti-fog switches on for the u6 duration.
-
if u1 = 2, r13 = 0 and the keypad is not locked, the key-operated load switches
on/off.
4.6
Key-operated load on/off (if u1 = 2 and r13 = 1)
1.
4.7
Silence buzzer (if A13 = 1)
Touch any key.
If u1 = 3 and u4 = 1, the alarm output switches off.
5
ADDITIONAL FUNCTIONS
5.1
Activate/deactivate overcooling, overheating and manual energy saving
Check that the keypad is not locked.
1.
FUNCTION
overcooling
overheating
energy saving
5.2
View/delete HACCP alarm information
Check that the keypad is not locked.
1.
2.
LAB.
LS
rLS
3.
4.
COD.
AL
AH
id
PF
5.
6.
MIN... MAX.
r1... r2
0 = °C
1 = °F
Example of alarm information (e.g. a high temperature alarm).
8.0
0 = electric
1 = hot gas
2 = compressor stopped
Sta
dur
5.3
View/delete compressor functioning hours and view compressor start-up
number
Check that the keypad is not locked.
1.
2.
LAB.
CH
rCH
nS1
3.
4.
5.
6.
with energy-saving strategies
OFF
FLASHING
compressor off
- compressor protection active
- setpoint setting active
-
- defrost delay active
- dripping active
evaporator fan off
evaporator fan stop active
-
new HACCP alarm saved
-
-
-
- settings active
- access to additional functions
active
-
overcooling or overheating active
auxiliary load off
- auxiliary load on by digital input
- auxiliary load delay active
device on
device on/off active
Touch the SET key.
Touch the UP or DOWN key within 15 s to set the value within
the limits r1 and r2 (default "-50... 50")
Touch the SET key (or do not operate for 15 s).
Touch the UP key for 2 s.
Touch the ON/STAND-BY key.
Touch the UP key.
Touch the DOWN key.
CONDITION
CONSEQUENCE
r5 = 0, r8 = 1 and defrost
the setpoint becomes "setpoint -
not active
r6", for the r7 duration
r5 and r8 = 1
the setpoint becomes "setpoint +
r6", for the r7 duration
r5 = 0 and r8 = 2
the setpoint becomes "setpoint +
r4", at maximum for HE2 duration
Touch the DOWN key for 4 s.
Touch the UP or DOWN key within 15 s to select a label.
DESCRIPTION
view HACCP alarm information
delete HACCP alarm information
Touch the SET key.
Touch the UP or DOWN key to select an alarm code (when label
"LS" is selected) or to set "149" (when label "rLS" is selected).
DESCRIPTION
low temperature alarm
high temperature alarm
door switch alarm
power failure alarm
Touch the SET key.
Touch the ON/STAND-BY key (or do not operate for 60 s) to exit
the procedure.
critical value (cabinet/ calculated product temperature)
was 8.0 °F/°C
y15
alarm signalled in 2015
n03
alarm signalled in March
d26
alarm signalled on 26 March 2015
h16
alarm signalled at 16:00
n30
alarm signalled at 16:30
h01
alarm lasted 1h
n15
alarm lasted 1h 15 min
Touch the DOWN key for 4 s.
Touch the UP or DOWN key within 15 s to select a label.
DESCRIPTION
view compressor functioning hours (hundreds)
delete compressor functioning hours
compressor start-up number (thousands)
Touch the SET key.
Touch the UP or DOWN key to set "149" (when label "rCH" is se-
lected).
Touch the SET key.
Touch the ON/STAND-BY key (or do not operate for 60 s) to exit
the procedure.
5.4
View the temperature detected by the probes
Check that the keypad is not locked.
1.
Touch the DOWN key for 4 s.
2.
Touch the UP or DOWN key within 15 s to select a label.
LAB.
DESCRIPTION
cabinet temperature (if P4 = 0, 1 or 2)
Pb1
inlet air temperature (if P4 = 3)
Pb2
evaporator temperature (if P3 = 1 or 2)
Pb3
auxiliary temperature (if P4 = 1, 2 or 3)
calculated product temperature (CPT) (if P4 = 3). See P7 in CONFIGURATION
Pb4
PARAMETERS for information.
3.
Touch the SET key.
Touch the ON/STAND-BY key (or do not operate for 60 s) to exit
4.
the procedure.
5.5
View the project number and the firmware revision
Check that the keypad is not locked.
1.
Touch the DOWN key for 4 s.
2.
Touch the UP or DOWN key within 15 s to select a label.
LAB.
DESCRIPTION
PrJ
view the project number
rEU
view the firmware revision
3.
Touch the SET key.
Touch the ON/STAND-BY key (or do not operate for 60 s) to exit
4.
the procedure.
6
SETTINGS
6.1
Setting configuration parameters
1.
Touch the SET key for 4 s: the display will show the label "PA".
2.
Touch the SET key. The display shows the label "PAS".
Touch the UP or DOWN key within 15 s to set the password. The
3.
default password is "-19".
Touch the SET key (or do not operate for 15 s): the display will
4.
show the label "SP".
5.
Touch the UP or DOWN key to select a parameter.
6.
Touch the SET key.
7.
Touch the UP or DOWN key within 15 s to set the value.
8.
Touch the SET key (or do not operate for 15 s).
Touch the SET key for 4 s (or do not operate for 60 s) to exit the
9.
procedure.
6.2
Set the date, time and day of the week
Important
Do not disconnect the device from the mains within two minutes since the setting of
the time and day of the week.
Check that the keypad is not locked.
1.
Touch the DOWN key for 4 s.
2.
Touch the UP or DOWN key within 15 s to select the label "rtc".
Touch the SET key: the display will show the label "yy" followed
3.
by the last two figures of the year.
4.
Touch the UP or DOWN key within 15 s to set the year.
5.
Repeat actions 3. and 4. to set the next labels.
LAB.
DESCRIPTION OF THE NUMBERS FOLLOWING THE LABEL
n
month (01... 12)
d
day (01... 31)
h
time (00... 23)
n
minute (00... 59)
Touch the SET key: the display will show the label for the day of
6.
the week.
Touch the UP or DOWN key within 15 s to set the day of the
7.
week.
LAB.
DESCRIPTION
Mon... Sun Monday... Sunday
8.
Touch the SET key: the device will exit the procedure.
9.
Touch the ON/STAND-BY key to exit the procedure beforehand.
6.3
Restore the factory settings (default) and store customized settings as default
Important
- Check that the factory settings are appropriate; see the section CONFIGURATION
PARAMETERS.
- When you store customized settings, you overwrite the default.
1.
Touch the SET key for 4 s: the display will show the label "PA".
2.
Touch the SET key.
3.
Touch the UP or DOWN key within 15 s to set the value.
VAL.
DESCRIPTION
149
value to restore the factory settings (default)
161
value to store customized settings as default
Touch the SET key (or do not operate for 15 s): the display will
4.
show the label "dEF" (when value "149" is set) or the label
"MAP" (when value "161" is set).
5.
Touch the SET key.
6.
Touch the UP or DOWN key within 15 s to set "4".
Touch the SET key (or do not operate for 15 s): the display will
7.
show for 4 s "- - -" flashing, then the device will exit the proce-
dure.
8.
Interrupt the power supply to the device.
Touch the SET key 2 s before action 6. to exit the procedure be-
9.
forehand.
7
CONFIGURATION PARAMETERS
N.
PAR.
DEF.
SETPOINT
1
SP
0.0
setpoint
N.
PAR.
DEF.
ANALOG INPUTS
2
CA1
0.0
cabinet probe offset
3
CA2
0.0
evaporator probe offset
4
CA3
0.0
auxiliary probe offset
5
P0
1
probe type
MIN... MAX.
r1... r2
MIN... MAX.
-25... 25 °F/°C
if P4 = 3, air in probe offset
-25... 25 °F/°C
-25... 25 °F/°C
0 = n/a
1 = NTC

Advertisement

loading

Summary of Contents for Penn TC3224N9R

  • Page 1 PENN | TC3224N9R | Installation Guide Rev. B | Part No. 24-7664-03531 | Page 1 of 3 | 07 April 2020 Controller for refrigerated cabinets, counters and islands, TC3224N9R with energy-saving strategies FLASHING View the temperature detected by the probes Check that the keypad is not locked.
  • Page 2 PENN | TC3224N9R | Installation Guide Rev. B | Part No. 24-7664-03531 | Page 2 of 3 | 07 April 2020 enable °C decimal point 0 = no 1 = yes power failure duration for alarm 0... 240 min MODBUS baud rate...
  • Page 3 PENN | TC3224N9R | Installation Guide Rev. B | Part No. 24-7664-03531 | Page 3 of 3 | 07 April 2020 PRODUCT WARRANTY This product is covered by a limited warranty, details of which can be found at www.johnsoncontrols.com/buildingswarranty SOFTWARE TERMS...