P66 Series Electronic Fan Speed Controls
Application
IMPORTANT: Use this P66 Series Electronic Fan
Speed Control only as an operating control. Where
failure or malfunction of the P66 control could lead to
personal injury or property damage to the controlled
equipment or other property, additional precautions
must be designed into the control system.
Incorporate and maintain other devices, such as
supervisory or alarm systems or safety or limit
controls, intended to warn of or protect against
failure or malfunction of the P66 control.
IMPORTANT: Utiliser ce P66 Series Electronic Fan
Speed Control uniquement en tant que dispositif de
contrôle de fonctionnement. Lorsqu'une défaillance
ou un dysfonctionnement du P66 control risque de
provoquer des blessures ou d'endommager
l'équipement contrôlé ou un autre équipement, la
conception du système de contrôle doit intégrer des
dispositifs de protection supplémentaires. Veiller
dans ce cas à intégrer de façon permanente d'autres
dispositifs, tels que des systèmes de supervision ou
d'alarme, ou des dispositifs de sécurité ou de
limitation, ayant une fonction d'avertissement ou de
protection en cas de défaillance ou de
dysfonctionnement du P66 control.
The P66 Series Electronic Fan Speed Controls are
pressure-actuated electronic motor-speed controllers
designed primarily to control condenser fan motors on
Heating, Ventilating, Air Conditioning, and
Refrigeration (HVAC/R) applications (Figure 1). These
controls vary the supply voltage to the fan motor in
response to the sensed refrigerant pressure, providing
direct response to changes in condenser pressure,
regardless of the variations in air delivery curves.
P66 controls are available with one or two pressure
sensor inputs. In dual sensor models, the control
selects the input with the greatest demand.
P66 control models are also available with NEMA 3R
(Rainproof) enclosures for outdoor applications
(Figure 1). These models come with a plastic
enclosure, appropriate gaskets, and low voltage wire
leads for 24 VAC power. In addition, the critical high
voltage components are encapsulated in a potting
compound.
© 2018 Johnson Controls
Part No. 24-7664-1482, Rev. G
Note:
NEMA 1 models cannot be retrofitted in the
field to obtain the NEMA 3R (Rainproof) rating.
A P66 and speed controlled motor can replace On/Off
fan cycling controls, multiple speed motors, condenser
flood-back systems, temperature fan-speed controls,
and modulating louver systems.
Typical applications include:
computer room air conditioning
commercial air conditioning
commercial refrigeration
The P66 Series controls must be applied only to
single-phase motors intended for use with a solid-state
motor speed control. An applicable motor must be a
single-phase, permanent split-capacitor motor and
must be:
ball-bearing construction only (Sleeve-bearing
motors are not acceptable for use with P66
controls.)
designed to handle non-sinusoidal waveforms
generated by solid-state motor speed controls
designed to dissipate the motor heat generated at
reduced speed operation
!
CAUTION: Risk of Property Damage.
Use only single-phase Permanent Split-Capacitor
(PSC) motors approved by the manufacturer for
speed control applications with the P66 control.
Failure to use a single-phase PSC motor may
damage the motor and other property.
MISE EN GARDE: Risque De dégâts matériels.
Utiliser uniquement les moteurs PSC (Permanent
Split-Capacitor) monophasés approuvés par le
fabricant pour les applications de régulation de
vitesse avec le régulateur P66. L'utilisation d'un
moteur autre qu'un moteur PSC monophasé risque
d'endommager le moteur et de provoquer d'autres
dégâts matériels
Installation Instructions
Issue Date September 2018
1

Advertisement

Table of Contents
loading

Summary of Contents for Penn P66AAB-1

  • Page 1 Installation Instructions Issue Date September 2018 P66 Series Electronic Fan Speed Controls Application Note: NEMA 1 models cannot be retrofitted in the IMPORTANT: Use this P66 Series Electronic Fan field to obtain the NEMA 3R (Rainproof) rating. Speed Control only as an operating control. Where A P66 and speed controlled motor can replace On/Off failure or malfunction of the P66 control could lead to fan cycling controls, multiple speed motors, condenser...
  • Page 2: Installation

    Installation WARNING: Risk of Personal Injury. Do not install the P66 Series Electronic Fan Speed Control in any application using corrosive or flammable refrigerants. The P66 control is not designed or intended for use with those refrigerants. Use of the P66 control with corrosive or flammable refrigerants may lead to the release of refrigerant, which could cause property damage, fire, severe personal injury, or death.
  • Page 3 Mounting Observe the following guidelines when mounting a • Locate the P66 control so the pressure elements P66 control and routing the control’s capillary tube: inside the base are above the refrigerant liquid level of the controlled equipment. • Mount the control where it can be conveniently CAUTION: Risk of Environmental and wired to the power supply and the motor.
  • Page 4 The P66 control must be supplied with 24 VAC (1 VA) from an external transformer powered from the same IMPORTANT: Use copper conductors only. Make all phase as the motor circuit (Figure 2, Figure 3, and wiring connections in accordance with the National Figure 4).
  • Page 5: Setup And Adjustments

    Setup and Adjustments The P66 control’s throttling range is fixed and cannot be adjusted. The operating range pressure is adjustable within the control pressure range. See the Technical Specifications table for P66 model pressure ratings. To adjust the operating range pressure: Apply a reliable pressure gauge to the controlled system to monitor the pressure adjustments.
  • Page 6: Pressure Input

    Preliminary—This information may change. 10% to 40% of Line No fan operation (model specific) in this pressure range. Pressure Input Operating Range Operating Range 350 psig psig (190/250 psig) Plus 20 or 30 psi* *20 psi for 30 psi Effective Throttling Range (ETR) 30 psi for 60 psi Effective Throttling Range (ETR) Figure 6: Operation Chart for the P66 Fan Speed Control Table 1: P66 Control Operation...
  • Page 7: Troubleshooting

    Field repairs must not be made. For a replacement control. control, contact the Original Equipment Manufacturer or your local Johnson Controls/PENN distributor. Place a jumper wire between third pin from the top and the bottom pin on the control, not the cable.
  • Page 8: Ordering Information

    Ordering Information Table 3: P66 Control Specific Model Information Product Code Operating Range Start Voltage Capillary Length (in.) Number (psig) (% of Supply Voltage) Single Input Sensor Models P66AAB-1 190/250 P66AAB-4 135/165 P66AAB-6 170/230 P66AAB-9 170/230 P66AAB-10 190/250 P66AAB-11 140/200...