Relay Output Screens - Emerson MultiFlex Series Installation And Operation Manual

I/o board
Table of Contents

Advertisement

the POINT (.) and DASH (-) keys to scroll
through the sensor types and units supported by
CPC controllers. Table 6-1 lists all the possible
engineering unit settings.
Field Value
Sensor Type
TEMP-DF
Temperature Sensor
TEMP-DC
Temperature Sensor
100-LB PSI
12V CPC 100-PSI
transducer
100-LB KPA
12V CPC 100-PSI
transducer
200-LB PSI
12V CPC 200-PSI
transducer
200-LB KPA
12V CPC 200-PSI
transducer
500-LB PSI
12V CPC 500-PSI
transducer
500-LB KPA
12V CPC 500-PSI
transducer
ECLP100-
5V 100-PSI pressure
transducer
PSI
ECLP100-
5V 100-PSI pressure
transducer
KPA
ECLP200-
5V 200-PSI pressure
transducer
PSI
ECLP200-
5V 200-PSI pressure
transducer
KPA
ECLP500-
5V 500-PSI pressure
transducer
PSI
ECLP500-
5V 500-PSI pressure
transducer
KPA
HUMIDITY-
Humidity sensor
RH
POWER-KW
Power transducer with
1-5V output (NOT
pulse count output)
REF LEAK
Refrigerant Leak
Transducer
DEW PT-DF
Dewpoint Probe
DEW PT-DC
Dewpoint Probe
LM235-DF
LM235 Temperature
Sensor
LM235-DC
LM235 Temperature
Sensor
Table 6-1 - Engineering Units for MultiFlex Inputs
MultiFlex I/O Board Hand-Held Terminal Screens
Field Value
REF LEVEL
LIQ LEVEL
LIGHT-FTC
Units
LIGHT-LUX
DF (°F)
PULSE
COUNT
DC (°C)
DIG-ON/OFF
PSI
LINEAR-V
KPA
HI-TEMP-DF
PSI
HI-TEMP-DC
KPA
SETPT ADJ
PSI
NOT USED
KPA
PSI
Table 6-1 - Engineering Units for MultiFlex Inputs
KPA

6.1.7. Relay Output Screens

PSI
KPA
PSI
KPA
WARNING! Point overrides performed by HHT are
not visible to or recognized by the MultiFlex's parent
RH (%)
controller. In some cases, this may cause unnecessary
proof failure alarms and other erroneous conditions. If
KW
a site controller is available, it is recommended all over-
rides be performed from the site controller instead of
the HHT.
PPM
The Relay Output Screens show the on/off
DF (°F)
status of the MultiFlex's relay outputs. The
DC (°C)
fields numbered R01 through R08 correspond to
DF (°F)
relay points #1 through #8 on the board.
Overriding a Relay Output
DC (°C)
You may temporarily override any relay out-
put to a fixed ON or OFF state using the Hand-
Held Terminal interface.
Sensor Type
Refrigerant Liquid
Level Probe (Hansen)
Analog Liquid Level
(Float-Type) Indicator
Light Level Sensor
Light Level Sensors
Pulse count input
Digital (ON/OFF) in-
put
Standard 0-5V Linear
Analog Input
Hi Temp Sensor
Hi Temp Sensor
Slide potentiometer
used for set point ad-
justment
Selecting this will
cause the input value
to read "UNUSED"
on the STATUS-ENG
UNITS screen.
R01: OFF
R02: OFF
R03: ON
R04: OFF
The MultiFlex Hand-Held Terminal Interface • 25
Units
PCT (%)
PCT (%)
FTC (foot-can-
dles)
LUX
None
ON/OFF
V
DF
DC
PCT (%)
None.