4.2 Periodic Inspection

Check the followings at regular intervals (every six months), or when operating environments has
changed.
WARNING
WARNING
Item
Power supply
Voltage of the power (measure at the terminal block of the
module)
Loose screws of power supply terminals
Check that wiring cable is not damaged
Installation
Check the base unit is securely attached to the chassis
condition
Check each module is securely attached to the base unit Not loose or no play
Check that the connector of cable is not loose and the
cable is not damaged
Around
Check that the functions of the nV-Tool are normal
nV-Tool
Check that the connector and the cable are not damaged Not loose or no damage
Around G2 I/O
Measure the voltage of each of the G2 I/O modules at the
module
terminal block
Check the LED of the input status display
Check the LED of the output status display
Check that the I/O terminal block is installed securely
Check that the terminal screws are not loose and the
terminals have a sufficient distance to the adjacent ones
Check that wiring cable is not damaged
Environment
Check that the temperature, humidity, vibration, dust, etc.
are within the specified range
When measuring the power supply voltage at the
terminal of the module, work so that the body does
not touch the terminal.
Otherwise, it may cause electric shock.
Do not modify/repair/disassemble/adjust the device,
module, or board.
It may cause electric shock, fire, injury, or failure.
Upon malfunction or failure, contact our branch office or service
office.
Table 4-2 Periodical checking items
Check points
Unified Controller nv Series FL-net Remote I/O Station Module FL654A User's Manual
4.2 Periodic Inspection
Mandatory
Prohibited
Corrective measures
PS691: 85 to 264Vac
PS693: 85 to 264Vac
PS632: 20.4 to 28.8Vdc
No loose screws
No damages to cables
Not loose or no play
No damages to cables
by executing simple operations
Within specifications
LEDs light normally
LEDs light normally
Not loose or no play
No danger of loose or contact
No damages to cables
Within general specifications
4