Toshiba FL654A User Manual page 100

Fl-net remote i/o station module
Table of Contents

Advertisement

Chapter 9 Maintenance Using nV-Tool
Code
Contents
0x0103
Text parameter
error
0x0104
Data read size
over
0x1101
STX/ETX error
9
0x1102
Text size error
0x1104
CRC error
0x3101
Control
command error
0x3102
Memory
command error
0x6102
FRAM
error
84
6F8C1625
Table 9-2 nV-Tool error(2)
In the specification of the transmission area,
・ Head address in Area1: beyond the limits of 0 to 511. (In the case of master station
calendar/Time setting function not used.).
・ Head address in Area1: beyond the limits of 0 to 504. (In the case of master station
calendar/Time setting function used.).
・ Area length in Area1: beyond the limits of 0 to 512. (In the case of master station
calendar/Time setting function not used.).
・ Area length in Area1: beyond the limits of 0 to 505. (In the case of master station
calendar/Time setting function used.)
・ The area specified by head address and the data length in Area1: beyond the limits of 0
to 511. (In the case of master station calendar/Time setting function not used.).
・ The area specified by head address and the data length in Area1: beyond the limits of 0
to 504. (In the case of master station calendar/Time setting function used.).
・ Head address in Area2: beyond the limits of 512 to 8703.
・ Area length in Area2: beyond the limits of 0 to 8192.
・ The area specified by head address and the data length in Area2: beyond the limits of
512 to 8703.
The com_num is not "log data clear: 1" in the operation history log command.
In time update the following state
・ Point block / point is not "point designation: 1"
・ Point number / block number is not "SYSCLOCK: 5"
・ Calendar / time data of data is abnormal
In the operation history log reading, the following state
・ The num_texts is not 5
・ The curtext_num is not 1 to 5
Received a transmission frame whose head is not STX from nV-Tool.
Received a transmission frame whose end is not ETX from nV-Tool.
The transmission frame received from nV-Tool exceeds 1021 bytes.
"MsgLen" in the transmission frame received from nV-Tool does not match the length of the
actually received transmission message.
A transmission frame received from nV-Tool has abnormal CRC code
mode
During TOOL operation, RUN/HALT switch status is RUN, I/O run mode, RUN command
received from nV-Tool.
During TOOL operation, RUN/HALT switch status is RUN, down mode, RUN command
received from nV-Tool.
During TOOL operation, the RUN/HALT switch status is HALT and the RUN command or
HALT command is received from nV-Tool.
During TOOL operation, RUN/HALT switch status is RUN, HALT mode, HALT command is
received from nV-Tool.
During TOOL operation, RUN/HALT switch status is RUN, DOWN mode, HALT command
is received from nV-Tool.
During TOOL operation, receive error reset command in I/O run mode.
During TOOL operation, error reset command is received in HALT mode.
Receive the RUN command from the nV-Tool in a state where the cyclic area of the I/O
configuration information is not within the range of the cyclic area of its own node
parameter.
IReceive RUN command from nV-Tool in a state where I/O configuration information is
abnormal.
clear
FL654A is set to TOOL specification; FL654A is received "memory clear" when FL654A is
I/O run mode or Down mode.
write
Writing in FRAM is failure or read-out from FRAM is failure.
Failed to read I/O configuration information or own node parameters from FRAM.
Factors

Advertisement

Table of Contents
loading

Table of Contents