Parameter Assignment And Structure Of The Module/Channel Parameters - Siemens SIMATIC ET 200SP HA Equipment Manual

Hide thumbs Also See for SIMATIC ET 200SP HA:
Table of Contents

Advertisement

Drivers, parameters, diagnostics messages and address space
A.2 Parameter assignment and structure of the module/channel parameters
Error_
Error_
Cause
Code_
Code_
1
2
0xE1
0x01
Reserved bit set
0xE1
0x02
Invalid diagnostics enable bit set for operating mode
0xE1
0x05
Invalid encoding for encoder type
0xE1
0x0B
Invalid coding for pulse stretching
0xE1
0x0E
Invalid redundancy parameter assignment
0xE1
0x21
Channel must be disabled due to change-over con‐
tact mode
0xE1
0x22
Encoder type "Change-over contact" is selected.
Select the value "Normal" for the "Digital input" pa‐
rameter.
0xE1
0x23
invalid coding of flutter monitoring
Valid parameters
Only the values specified in the following are permitted. Values that are not listed are rejected
by the module.
Every parameter data record is checked by the module. If an incorrect parameter is detected, the
entire data record is rejected and the parameters of the module remain unchanged.
A.2
Parameter assignment and structure of the module/channel
parameters
Structure of data record 128
Data record 128 has a length of 108 bytes.
It contains module parameters as well as channel or technology parameters of the 16 channels;
6 bytes each.
The channel or technology parameters are divided into parameters that affect the actual signal
acquisition or settings and diagnostics enables.
42
Remedy
Check and correct the parameters
Equipment Manual, 08/2019, A5E39293880-AD
DI 16xNAMUR HA

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Simatic di 16xnamur ha6dl1131-6th00-0ph1

Table of Contents