Alarm Parameters; Extended Relaying - Siemens WL Series Selection And Application Manuallines

Low voltage circuit breaker
Table of Contents

Advertisement

Low Voltage Circuit Breaker
Electronic trip unit (ETU)

Alarm parameters

The metering function includes the following alarm
set-point functions:
Alarm function
Overcurrent
Overcurrent – ground fault
Overcurrent – N-conductor
Phase unbalance – current
Demand – current
Total harmonic distortion - current
Undervoltage
Overvoltage
Phase unbalance - voltage
Total harmonic distortion - voltage
Crest factor
Form factor
Active power in normal direction
Active power in reverse direction
Leading power factor
Lagging power factor
Demand - active power
Apparent power
Reactive power in normal direction
Reactive power in reverse direction
Demand - apparent power
Demand - reactive power
Underfrequency
Overfrequency

Extended relaying

Protective relays included with the metering function can
monitor the following criteria and initiate a trip if the values
are exceeded.
Protective relay function
Current unbalance
Total harmonic distortion - current
Voltage unbalance
Undervoltage
Overvoltage
Total harmonic distortion - voltage
Direction of phase rotation
Active power in normal direction
Active power in reverse direction
Under frequency
Over frequency
WL Circuit Breaker selection and application guide
Setting range
3 ... 10000A
3 ... 10000A
3 ... 10000A
5 ... 50%
3 ... 10000A
0 ... 50%
100...1200V
200...1200V
5 ... 50%
0 ... 50%
0.01 ... 25.5%
0.01 ... 25.5%
1 ... 10000kW
1 ... 10000kW
-0.999 ... 1
-0.999 ... 1
1 ... 10000kW
1 ... 10000kVA
1 ... 10000kvar
1 ... 10000kvar
1 ... 10000kVA
1 ... 10000kvar
40 ... 70 Hz
40 ... 70 Hz
ANSI device number
46
81 THDC
47
27
59
81 THDV
47N
32
32R
81U
81O
Possible delay
0 ... 255 s
0 ... 255 s
0 ... 255 s
0 ... 255 s
0 ... 255 s
5 ... 255 s
0 ... 255 s
0 ... 255 s
0 ... 255 s
5 ... 255 s
0 ... 255 s
0 ... 255 s
0 ... 255 s
0 ... 255 s
0 ... 255 s
0 ... 255 s
0 ... 255 s
0 ... 255 s
0 ... 255 s
0 ... 255 s
0 ... 255 s
0 ... 255 s
0 ... 255 s
0 ... 255 s
Setting range
5 ... 50%
0 ... 50%
5 ... 50%
100 ... 1100V
200 ... 1200V
0 ... 50%
1 ... 10000kW
1 ... 10000kW
40 ... 70 Hz
40 ... 70 Hz
Possible delay
1 ...15 s
5 ...15 s
1 ...15 s
1 ...15 s
1 ...15 s
5 ...15 s
1 ...15 s
1 ...15 s
1 ...15 s
1 ...15 s
9