Drivers, parameters, diagnostics messages and
address space
A.1

Parameter assignment

Parameter assignment in the user program
You can re-parameterize individual channels of the module in RUN without this having an effect
on the other channels.
Changing parameters in RUN
The "WRREC" instruction is used to transfer the parameters to the module using data record 128.
Output parameter STATUS
If errors occur when transferring parameters with the "WRREC" instruction, the module
continues operation with the previous parameter assignment. The STATUS output parameter
contains the corresponding error code.
The STATUS output parameter is 4 bytes long and is configured as followed:
• Byte1: Function_Num, general error code
• Byte2: Error_Decode, location of the error code
• Byte3: Error_Code_1, error code
• Byte4: Error_Code_2, manufacturer-specific extension of the error code
Module-specific errors are displayed via Error_Decode = 0x80 and Error_Code_1 / Error_Code_2.
Error_
Error_
Cause
Code_
Code_
1
2
0xB0
0x00
Number of the data record unknown
0xB1
0x01
Length of the data record is incorrect
0xB2
Varia‐
Module cannot be reached
ble
0xE0
0x01
Wrong version in the header
0xE0
0x02
Header error (number or length of parameter block) Correct the length and number of the parameter
DI 16xNAMUR HA
Equipment Manual, 08/2019, A5E39293880-AD
Remedy
Enter valid number for data record.
Enter valid value for data record length.
Check station - is the module plugged in cor‐
rectly?
Check the parameters of the WRREC instruction.
Correct the version number of the parameter block.
blocks.