Behavior of switch output and signaling
MAX
MIN
 23
Behavior of switch output and signaling, electronic insert FEL64
MAX DIP switch for setting MAX safety mode
MIN DIP switch for setting MIN safety mode
RD
LED red for alarm
YE
LED yellow, switch status
GN LED green, operational status, device on
6.2.4
DC connection, relay output (electronic insert FEL64 DC)
• Switches the loads via 2 potential-free changeover contacts
• Two galvanically isolated change-over contacts (DPDT), both change-over contacts
switch simultaneously
• Functional testing without level change. Functional testing of the entire device can be
performed using the test button on the electronic insert or with the test magnet (can be
ordered as an option) with the housing closed.
Supply voltage
U = 9 to 20 V
DC
Observe the following as per IEC/EN61010-1: Provide a suitable circuit breaker for
the device, and limit the current to 500 mA, e. g. by installing a 0.5 A fuse (slow-
blow) in the supply circuit.
Power consumption
P < 1.0 W
Connectable load
Loads switched via 2 potential-free changeover contacts (DPDT)
• I
≤ 6 A (Ex de 4 A), U~ ≤ AC 253 V; P~ ≤ 1 500 VA, cos φ = 1, P~ ≤ 750 VA, cos φ > 0.7
AC
• I
≤ 6 A (Ex de 4 A) to DC 30 V, I DC ≤ 0.2 A to 125 V
DC
According to IEC 61010, the following applies: Total voltage from relay outputs and power
supply ≤ 300 V
Preferably use electronic insert FEL62 DC PNP for low DC current loads, e. g. connection to
a PLC.
Relay contact material: silver/nickel AgNi 90/10
RD
YE
GN
3
4
5
3
4
5
3
4
5
3
4
5
3
4
5
Electrical connection
6
7
8
6
7
8
6
7
8
6
7
8
6
7
8
A0033513
23