DAMA-SM-21-003
5.11 Power Module Check
Check No.22
Check to make sure that the voltage between (+) and (–) of the power module is approximately
0 V before checking.
Disconnect the compressor (X12A)/fan motor (X11A) harness connector from the outdoor
Follow the procedure below to measure resistance between the (+) or (–) terminal of the
Positive terminal (+) of
digital multimeter
Negative terminal (–) of
digital multimeter
Resistance is OK.
Resistance is NG.
Positive terminal (+) of
digital multimeter
Negative terminal (–) of
digital multimeter
Resistance is OK.
Resistance is NG.
Service Diagnosis
unit PCB. To disengage the connector, press the protrusion on the connector.
power module and the U, V, or W terminal of the compressor (X12A)/fan motor (X11A) with
a multimeter. Evaluate the measurement results referring to the following table.
Power module
Power module
Diagram Power Module Check for CTX07/09/12
Compressor
UVW
(+)
Power module
UVW
(+)
several kΩ ~ several MΩ
0 Ω or ∞
Fan motor
UVW
(+)
Power module
UVW
(+)
several kΩ ~ several MΩ
0 Ω or ∞
Fan motor
Pin 28: +
Pin 31: U
Pin 35: V
Pin 37: W
Pin 40: -
Actuator Check
Power module
UVW
(–)
Power module
UVW
(–)
Power module
UVW
(–)
Power module
UVW
(–)
Compressor
Pin 24: +
Pin 23: U
Pin 22: V
Pin 21: W
Pin 20: -
91