INSTALLATION MANUAL ZQ SERIES 3 - 5 ton 60 Hertz R-410A York International Corporation, 5005 5943355-UIM-A-1020 York Drive, Norman, OK 73069 2020-10-01 Johnson Controls Ducted Systems...
Page 2
INSTALLATION MANUAL ZQ SERIES 3 - 5 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
Power interruptions..........73 Gas Connection..........40 Flame present with Gas off........73 Combustion Air and Flue Exhaust....41 Welded gas valve relay response......73 Options/Accessories..........42 Start-Up (Cooling)............74 INSTALLATION MANUAL ZQ SERIES 3 - 5 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
Page 4
Adjustment Of Temperature Rise........ 78 Burners/Orifices Inspection/Servicing......79 Start up for Units Equipped for FER......80 Direct Drive..............80 Troubleshooting..............81 Charging Tables............. 84 Control Board Navigation Components......86 Start-Up Sheet..............87 INSTALLATION MANUAL ZQ SERIES 3 - 5 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
This product must be installed in strict compliance with the installation instructions and any applicable local, state and national codes including, but not limited to building, electrical, and mechanical codes. INSTALLATION MANUAL ZQ SERIES 3 - 5 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
Vertical Flow Dry Bulb Economizer Field writing. Installed Horizontal Flow Dry Bulb Economizer Field Installed Renewal Parts Contact your local Ducted Systems parts distribution center for authorized replacement parts. INSTALLATION MANUAL ZQ SERIES 3 - 5 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
This product must be installed in strict compliance with the enclosed installation instructions and any applicable local, state, and national codes including, but not limited to, building, electrical, and mechanical codes. INSTALLATION MANUAL ZQ SERIES 3 - 5 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
Change tap on transformer for 208-3-60 operation. See the unit wiring diagram. Remove the two screws that hold the brackets in the forklift slots on the side of the unit. INSTALLATION MANUAL ZQ SERIES 3 - 5 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
Page 10
Figure 5 for the sensor relocation. down) to the working position (right side up). Then slide the flex tube over the stub and tighten, see Figure 7. INSTALLATION MANUAL ZQ SERIES 3 - 5 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
Edition east side of building. • Gas-Fired Central Furnace Standard, ANSI Suitable for mounting on roof curb. Z21.47a. - Latest Edition INSTALLATION MANUAL ZQ SERIES 3 - 5 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
Refer to Table 4 for clearances required for combustible construction, servicing, and proper unit operation. WARNING Do not permit overhanging structures or shrubs to obstruct condenser air discharge outlet, combustion air inlet or vent outlets. INSTALLATION MANUAL ZQ SERIES 3 - 5 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
Hail Guard Kit Small Short Factory Installed Hail Guard Kit Small Tall Factory Installed Flue Extension Kit (1FE0414) Flue Extension Kit (1FE0415) Curb Rigid 14 in. Small Footprint Curb Rigid 24 in. Small Footprint INSTALLATION MANUAL ZQ SERIES 3 - 5 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
Page 14
Figure 11: ZQ04-05 Unit Dimensions INSTALLATION MANUAL ZQ SERIES 3 - 5 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
Page 15
Figure 12: ZQ06 Unit Dimensions INSTALLATION MANUAL ZQ SERIES 3 - 5 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
They should NOT be sized 1TB0403 - Thru the base electrical and gas to match the dimensions of the duct connections on the unit. INSTALLATION MANUAL ZQ SERIES 3 - 5 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
Install Note: Shown with duct connection cover panel condensate drain line from the 3/4 in. NPT female as shipped. connection on the unit to an open drain. INSTALLATION MANUAL ZQ SERIES 3 - 5 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
Rating Plate and R-410A compressor lubricants are known to cause Table 1. long term damage to some synthetic roofing materials. INSTALLATION MANUAL ZQ SERIES 3 - 5 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
The above water-proofing conditions will also apply when installing a field supplied disconnect switch. INSTALLATION MANUAL ZQ SERIES 3 - 5 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
Typical Field Power and Control Wiring Typical Power Wiring Figure 18: Everyday Thermostat Control (ETC) typical power wiring INSTALLATION MANUAL ZQ SERIES 3 - 5 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
Page 21
Figure 19: Typical Smart Equipment™ Control Wiring INSTALLATION MANUAL ZQ SERIES 3 - 5 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
Page 23
Non-fused Disconnect, Verify on the unit nameplate that the disconnect is properly sized for the application. Units with field installed electric heat kits may exceed the factory installed disconnect amperage rating. INSTALLATION MANUAL ZQ SERIES 3 - 5 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
Page 25
Non-fused Disconnect, Verify on the unit nameplate that the disconnect is properly sized for the application. Units with field installed electric heat kits may exceed the factory installed disconnect amperage rating. INSTALLATION MANUAL ZQ SERIES 3 - 5 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
Page 27
Non-fused Disconnect, Verify on the unit nameplate that the disconnect is properly sized for the application. Units with field installed electric heat kits may exceed the factory installed disconnect amperage rating. INSTALLATION MANUAL ZQ SERIES 3 - 5 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
Page 29
Non-fused Disconnect, Verify on the unit nameplate that the disconnect is properly sized for the application. Units with field installed electric heat kits may exceed the factory installed disconnect amperage rating. INSTALLATION MANUAL ZQ SERIES 3 - 5 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
Non-fused Disconnect, Verify on the unit nameplate that the disconnect is properly sized for the application. Units with field installed electric heat kits may exceed the factory installed disconnect amperage rating. INSTALLATION MANUAL ZQ SERIES 3 - 5 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
Page 31
Non-fused Disconnect, Verify on the unit nameplate that the disconnect is properly sized for the application. Units with field installed electric heat kits may exceed the factory installed disconnect amperage rating. INSTALLATION MANUAL ZQ SERIES 3 - 5 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
Non-fused Disconnect, Verify on the unit nameplate that the disconnect is properly sized for the application. Units with field installed electric heat kits may exceed the factory installed disconnect amperage rating. INSTALLATION MANUAL ZQ SERIES 3 - 5 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
Page 33
Non-fused Disconnect, Verify on the unit nameplate that the disconnect is properly sized for the application. Units with field installed electric heat kits may exceed the factory installed disconnect amperage rating. INSTALLATION MANUAL ZQ SERIES 3 - 5 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
Unit Capacity Steps (%) Face area (Sq. Ft.) 16.3 16.3 Rows CONDENSER COIL DATA Fins per inch Tube diameter (in./MM) .63/16 .63/16 Circuitry Type 2-pass Microchannel 2-pass Microchannel INSTALLATION MANUAL ZQ SERIES 3 - 5 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
Page 35
2 - (16 x 25 x 2) 2 - (16 x 25 x 2) FILTERS Quantity - Size 2 in. Throwaway, Standard, MERV 4 (Minimum Efficiency Reporting Value) INSTALLATION MANUAL ZQ SERIES 3 - 5 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
Page 36
Unit Capacity Steps (%) Face area (Sq. Ft.) 16.3 16.3 Rows CONDENSER COIL DATA Fins per inch Tube diameter (in./MM) .63/16 .63/16 Circuitry Type 2-pass Microchannel 2-pass Microchannel INSTALLATION MANUAL ZQ SERIES 3 - 5 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
Page 37
2 - (16 x 25 x 2) 2 - (16 x 25 x 2) FILTERS Quantity - Size 2 in. Throwaway, Standard, MERV 4 (Minimum Efficiency Reporting Value) INSTALLATION MANUAL ZQ SERIES 3 - 5 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
Page 38
Unit Capacity Steps (%) Face area (Sq. Ft.) 21.1 21.1 Rows CONDENSER COIL DATA Fins per inch Tube diameter (in./MM) .71/18 .71/18 Circuitry Type 2-pass Microchannel 2-pass Microchannel INSTALLATION MANUAL ZQ SERIES 3 - 5 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
Page 39
4 - (16 x 16 x 2) 4 - (16 x 16 x 2) FILTERS Quantity - Size 2 in. Throwaway, Standard, MERV 4 (Minimum Efficiency Reporting Value) INSTALLATION MANUAL ZQ SERIES 3 - 5 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
1 in. 1 1/4 in. 1050 flexible gas appliance connector, always use a new listed connector. Do not use a connector which has previously serviced another gas appliance. INSTALLATION MANUAL ZQ SERIES 3 - 5 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
See Figure 21 for location of hood within the unit and Figure 22 for installation of the hood. If necessary, a flue exhaust extension may be installed at the point of installation. INSTALLATION MANUAL ZQ SERIES 3 - 5 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
Economizer accessories include complete instructions for installation. There are two Economizer options. Each is specific to footprint and unit voltage: Vertical Flow application with barometric relief standard. INSTALLATION MANUAL ZQ SERIES 3 - 5 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
Note: Check all three phase motors and compressors for proper rotation after making a change. If it is necessary to change 3 phase motor rotation, swap A or L1 and C or L3 only. INSTALLATION MANUAL ZQ SERIES 3 - 5 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
Page 45
Sea level static pressure = 0.6 / .832 = 0.72 in. Enter the blower table at 1,400 sCFM and static pressure of 0.72 in. The rpm listed will be the same rpm needed at 5,000 ft. INSTALLATION MANUAL ZQ SERIES 3 - 5 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications. Note: See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP. kW = 0.929 x BHP INSTALLATION MANUAL ZQ SERIES 3 - 5 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications. Note: See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP. kW = 0.929 x BHP INSTALLATION MANUAL ZQ SERIES 3 - 5 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
Verify proper sheave alignment; tighten blower pulley the new motor sheave, and motor sheave set screws after these adjustments. Re-checking set screws and belt tension after 10-12 hrs. run time is recommended. INSTALLATION MANUAL ZQ SERIES 3 - 5 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
Page 53
The pressure drop through the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return air duct is less than 0.25 IWG, the unit will deliver less CFM during full economizer operation. INSTALLATION MANUAL ZQ SERIES 3 - 5 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
Thermostat Connection Alarm Indication (24VAC Rectified) Thermostat Connection 24VAC Connection Thermostat Connection No Connection Thermostat Connection 24VAC Common ConnectionLimit For Internal Use Only No Connection (For Future Use) INSTALLATION MANUAL ZQ SERIES 3 - 5 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
Page 55
VFD will run at 67% speed. When Y2 is energized, FAN2 output 2 will energize and the VFD will run at 100% (but only if C1 is “on”). INSTALLATION MANUAL ZQ SERIES 3 - 5 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
Page 56
ETC, 24VAC will be applied to FAN1 output, and 6VDC will be applied to VFD output to produce 50% fan speed. INSTALLATION MANUAL ZQ SERIES 3 - 5 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
SD-24 and R 24 VAC common for thermostat power INSTALLATION MANUAL ZQ SERIES 3 - 5 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
Page 58
Input required for operation of 2-compressor units, not active for 1-compressor units; 3.625 EC2+ input from 10KΩ @ 77°F, Type III negative temperature VDC reading EC2+ to EC2– with open circuit. Used in suction line temperature safety. coefficient thermistor INSTALLATION MANUAL ZQ SERIES 3 - 5 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
Page 59
Not effective for one stage compressor UCBs. If demand is present and permissions 24 VAC hot output for compressor 2 allow compressor 2 operation; output with compressor cooling, comfort ventilation cooling or heat pump heating demands INSTALLATION MANUAL ZQ SERIES 3 - 5 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
Page 60
FDD board parameters ENTER Button for display menu acknowledgment and navigation Button for display menu navigation and zeroing of active compressor CANCEL ASCD timer 4-way Joystick for display menu navigation INSTALLATION MANUAL ZQ SERIES 3 - 5 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
Page 61
Be sure the cable you use fits the modular jack housing. The preassembled cables that are available from Anixter (Part No. CBL-NETWORKxxx) use 24 gauge wire. INSTALLATION MANUAL ZQ SERIES 3 - 5 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
26°F and the anti- Otherwise, the unit operates until the minimum short cycle delay (ASCD) must have elapsed. run has been completed. Upon the compressor INSTALLATION MANUAL ZQ SERIES 3 - 5 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
Page 63
UCB will de-energize the compressor, initiate the actuator position exceeds the exhaust fan set point ASCD, and stop the condenser fan. on the economizer control. When the power exhaust INSTALLATION MANUAL ZQ SERIES 3 - 5 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
Page 64
An Anti- operated throughout the cycle. The 5-minute off Short Cycle Delay (ASCD) is utilized to prevent period is necessary to defrost the indoor coil. INSTALLATION MANUAL ZQ SERIES 3 - 5 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
UCB will energize the blower correct. Too high of a setting will result in longer motor. heat cycles and a greater temperature swing in the conditioned space. Reducing the value below the INSTALLATION MANUAL ZQ SERIES 3 - 5 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
2 of the S3 connector on the (UCB) unit control board to P2-4 on the ignition control board. Cut the wire 1/2 in. from the S3 mate-n-lock INSTALLATION MANUAL ZQ SERIES 3 - 5 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
Page 67
22. No Alarms in Memory 2 pulses 2 pulses 23. Normal Idle Slow Heartbeat 24. Factory Test Mode Rapid Flash Rapid Flash INSTALLATION MANUAL ZQ SERIES 3 - 5 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
Page 68
C; at least 0.25 volts higher than –) SA BUS communication circuit to the UCB. Through the unit wiring harness, may continue on to the 4-stage board and/or fault detection & diagnostics board INSTALLATION MANUAL ZQ SERIES 3 - 5 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
Page 69
Connects through circuit trace to 24V~ IN pin COM station sensor 24V~ 24 VAC hot supplied for the building pressure sensor Connects through circuit trace to 24V~ IN pin HOT INSTALLATION MANUAL ZQ SERIES 3 - 5 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
If 24 V is not received on the MV terminal within 6 minutes, an alarm appears and the fan output energizes immediately and remains On until the alarm clears. INSTALLATION MANUAL ZQ SERIES 3 - 5 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
Page 71
LIMIT input 3 times in 1 hour, an alarm appears and the FAN output is energized. The heating H1 and H2 outputs are de-energized until the alarm is cleared. INSTALLATION MANUAL ZQ SERIES 3 - 5 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
If low pressure switch opens, the control de- trial. The control de-energizes the spark when flame energizes the gas valve and begins pressure switch is sensed and enters a flame stabilization period. proving mode. INSTALLATION MANUAL ZQ SERIES 3 - 5 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
If the limit switch recloses in this hard lockout condition, the inducer will run a post purge and then shutoff. The control shall remain INSTALLATION MANUAL ZQ SERIES 3 - 5 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
First stage compressors will energize after the built-in time delay (five minutes). Post Start Check List Verify proper system pressures. Measure the temperature drop across the evaporator coil. INSTALLATION MANUAL ZQ SERIES 3 - 5 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
After the entire control circuit has been energized and the heating section is operating, make the following checks: Check for gas leaks in the unit piping as well as the supply piping. INSTALLATION MANUAL ZQ SERIES 3 - 5 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
Measure the time needed for one revolution of the hand on the lowest increment dial on the meter. A typical gas meter has a 1/2 or a 1 cubic foot test dial. INSTALLATION MANUAL ZQ SERIES 3 - 5 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
Turn off all power to the unit. stage heat. Using the outlet pressure port on the gas valve, connect a manometer to monitor the manifold pressure. INSTALLATION MANUAL ZQ SERIES 3 - 5 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
Physical data. After the temperature rise has been determined, the CFM can be calculated as follows: INSTALLATION MANUAL ZQ SERIES 3 - 5 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
National Standard of Canada, Natural Gas supports. Burners are now accessible for and Propane Installation Code, CSA B149.1. inspection and/or replacement. Figure 30: 3 Thru 5 Ton, 1/2” Single Stage Gas Valve INSTALLATION MANUAL ZQ SERIES 3 - 5 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
Note: During installation, the tap chosen for the heating speed must produce a temperature rise that lies within the rise range stated on the rating plate and the physical data tables. INSTALLATION MANUAL ZQ SERIES 3 - 5 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
60 minute excessive voltage, RF interference, etc. should be investigated. "watchdog" timer. INSTALLATION MANUAL ZQ SERIES 3 - 5 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
Page 82
Verify wiring for main and auxiliary limit switches is intact. INSTALLATION MANUAL ZQ SERIES 3 - 5 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
Page 83
1 second at the first stage and/or second stage gas valve output (P1-7 pin and/or P1-4 pin) when the gas valve is commanded on by the ignition control INSTALLATION MANUAL ZQ SERIES 3 - 5 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
Smart Equipment™ Quick Start Guide. Note: For more in-depth sequence of operation of the Smart Equipment™ control, refer to the Smart Equipment™ Controls Sequence of Operation Overview LIT-12011950. INSTALLATION MANUAL ZQ SERIES 3 - 5 ton 60 Hertz R-410A Johnson Controls Ducted Systems...