York International ZQ Series Installation Manual page 85

Table of Contents

Advertisement

Table 65: ZQ06 Charging Table
Air Flow Indoor Db/Wb
Outdoor DB ° F
75
300 Cfm/Ton 80/62
85
95
75
300 Cfm/Ton 80/67
85
95
75
300 Cfm/Ton 80/72
85
95
75
300 Cfm/Ton 75/62
85
95
75
400 Cfm/Ton 80/62
85
95
75
400 Cfm/Ton 80/67
85
95
75
400 Cfm/Ton 80/72
85
95
75
400 Cfm/Ton 75/62
85
95
Suction P psig
Suction Temp. ° F
135
67
136
65
137
63
135
68
139
67
143
66
136
68
143
69
150
70
130
63
132
61
135
60
138
70
141
69
144
68
139
70
144
70
148
70
140
70
146
71
151
72
134
66
137
65
140
64
INSTALLATION MANUAL ZQ SERIES 3 - 5 ton 60 Hertz R-410A
Johnson Controls Ducted Systems
Liquid P psig
Liquid Temp. ° F
282
77
324
88
365
99
282
77
326
88
370
98
282
77
329
87
376
98
279
78
321
88
363
99
285
77
328
88
371
98
286
77
330
87
374
98
287
77
332
87
377
97
282
77
325
88
369
98
Delta T Db ° F
Compr. amps
-25
14.1
-26
15.9
-27
17.7
-25
14.2
-25
16.1
-24
18.0
-26
14.2
-23
16.1
-21
18.1
-23
14.0
-23
15.8
-23
17.7
-23
14.3
-23
16.2
-23
18.1
-22
14.4
-21
16.2
-21
18.1
-22
14.4
-20
16.3
-19
18.1
-20
14.2
-20
16.1
-19
17.9