4.
When the thermostat heat inputs are lost and
the 120 second Minimum Heat Run Timers
have expired, heating outputs stage off. The
FAN OFF HEAT DELAY timer starts when 24 V
is removed from the MV terminal. When the
timer expires, the FAN output for the indoor
fan operation de-energizes.
Note: If 24 V is lost on the MV terminal
during the same heat cycle, an alarm
appears and the fan output energizes
and remains On until 24 V is present
again on the MV terminal.
Note: If 24 V is present on the MV
terminal without a call for heat, an alarm
appears and the fan output energizes.
If this condition occurs for 6 minutes an
alarm appears, and remains, until the
alarm condition is cleared.
5.
At any time, if 24 V is lost on the LIMIT
terminal, the FAN output for indoor fan
operation is energized. If 24 V is lost on
the LIMIT input 3 times in 1 hour, an alarm
appears and the FAN output is energized. The
heating H1 and H2 outputs are de-energized
until the alarm is cleared.
INSTALLATION MANUAL ZQ SERIES 3 - 5 ton 60 Hertz R-410A
Johnson Controls Ducted Systems
71