Zq04-06 Bottom Duct Application (Belt Drive) - York International ZQ Series Installation Manual

Table of Contents

Advertisement

Table 29: ZQ04-06 Side Duct (Gas Heat)
Unit (Ton)
Motor Speed
CFM
1 (LOW)
1570
2 (MED/LOW)
1740
ZQ06 (5)
3 (MED)
1882
4 (MED/HI)
2052
5 (HI)
2227

ZQ04-06 Bottom Duct Application (Belt Drive)

Table 30: ZQ04 (3.0 Ton) Bottom Duct
CFM
0.2
0.4
RPM
BHP
RPM
BHP
900
792
0.14
879
0.25
1000
804
0.18
893
0.29
1100
819
0.23
909
0.34
1200
837
0.29
926
0.40
1300
857
0.36
946
0.46
1400
880
0.43
969
0.53
1500
905
0.50
994
0.61
Medium Static Option with Motor rated at 2.4-hp
High Static Option with Motor rated at 2.4-hp
--
Exceeds recommended Blower speed
1
Blower performance includes gas heat exchangers and 2" filters. See STATIC RESISTANCE table for additional applications. Note:
See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP. kW = 0.929
x BHP
Table 31: ZQ05 (4.0 Ton) Bottom Duct
CFM
0.2
0.4
RPM
BHP
RPM
BHP
1200
908
0.34
994
0.45
1300
921
0.40
1007
0.51
1400
938
0.47
1023
0.58
1500
959
0.55
1044
0.65
1600
985
0.63
1070
0.73
1700
1015
0.71
1100
0.82
1800
1050
0.81
1136
0.91
1900
1091
0.91
1176
1.02
2000
1136
1.02
1222
1.13
Medium Static Option with Motor rated at 2.4-hp
High Static Option with Motor rated at 2.4-hp
Field supplied AK41 x 3/4" fixed blower pulley with Motor rated at 2.4-hp
--
Exceeds recommended blower speed
1
Blower performance includes gas heat exchangers and 2" filters. See STATIC RESISTANCE table for additional applications. Note:
See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP. kW = 0.929
x BHP
0.2
0.4
WATTS
RPM
CFM
WATTS
372
791
1463
399
468
845
1638
496
569
889
1786
601
732
955
1967
749
905
1004
2138
937
AVAILABLE EXTERNAL STATIC PRESSURE - IWG
0.6
0.8
RPM
BHP
RPM
BHP
RPM
968
0.37
1055
0.49
1141
981
0.41
1069
0.53
1155
997
0.46
1084
0.58
1171
1015
0.52
1102
0.64
1188
1035
0.58
1122
0.70
1208
1058
0.65
1145
0.77
1231
1082
0.73
1170
0.85
1256
AVAILABLE EXTERNAL STATIC PRESSURE - IWG
0.6
0.8
RPM
BHP
RPM
BHP
RPM
1072
0.55
1145
0.64
1214
1085
0.61
1158
0.70
1227
1101
0.68
1174
0.77
1244
1122
0.75
1195
0.85
1265
1148
0.83
1221
0.93
1290
1179
0.92
1251
1.01
1321
1214
1.01
1287
1.11
1356
1254
1.12
1327
1.21
1397
1300
1.23
1372
1.32
1442
Johnson Controls Ducted Systems
Available External Static
0.6
RPM
CFM
WATTS
RPM
855
1358
425
918
903
1543
529
965
947
1687
629
1002
999
1883
778
1049
1051
2038
947
1091
1
1.0
1.2
1.4
BHP
RPM
BHP
RPM
BHP
0.61
1226
0.73
1308
0.84
0.66
1239
0.77
1322
0.88
0.71
1255
0.82
1337
0.93
0.76
1273
0.88
1355
0.99
0.83
1293
0.94
1375
1.05
0.90
1315
1.02
1398
1.12
0.97
1340
1.09
1423
1.20
1
1.0
1.2
1.4
BHP
RPM
BHP
RPM
BHP
0.74
1283
0.83
1352
0.92
0.80
1296
0.89
1365
0.98
0.86
1312
0.96
1382
1.05
0.94
1333
1.03
1403
1.12
1.02
1359
1.11
1428
1.20
1.11
1389
1.20
1459
1.29
1.20
1425
1.29
1494
1.39
1.31
1465
1.40
1534
1.49
1.42
1510
1.51
1580
1.60
INSTALLATION MANUAL ZQ SERIES 3 - 5 ton 60 Hertz R-410A
0.8
CFM
WATTS
RPM
CFM
WATTS
1260
456
983
1161
1454
553
1015
1360
1587
660
1053
1487
1788
808
1099
1621
1869
887
1118
1662
1.6
1.8
RPM
BHP
RPM
BHP
1388
0.93
1466
1.01
1402
0.98
1480
1.05
1418
1.03
1495
1.10
1435
1.08
1513
1.16
1455
1.15
1533
1.22
1478
1.22
1556
1.29
1503
1.30
1581
1.37
1.6
1.8
RPM
BHP
RPM
BHP
1424
1.01
1502
1.11
1437
1.07
1514
1.17
1454
1.14
1531
1.23
1475
1.21
1552
1.31
1500
1.29
1578
1.39
1531
1.38
1608
1.48
1566
1.48
1644
1.57
1607
1.58
--
--
--
--
--
--
1.0
RPM
481
1044
578
1070
680
1105
778
1130
811
1137
2.0
RPM
BHP
1541
1.06
1554
1.10
1570
1.15
1588
1.21
--
--
--
--
--
--
2.0
RPM
BHP
1586
1.20
1599
1.26
1616
1.33
1637
1.41
--
--
--
--
--
--
--
--
--
--
49