York International ZQ Series Installation Manual page 59

Table of Contents

Advertisement

Table 46: Smart Equipment™ UCB - pinned connections
Location
Label
RAH+
Return Air Humidity input from 0-10 VDC @ 0-100% RH sensor
DCT PRS+
Supply Duct Pressure input from 0-5 VDC @ 0-5" w.c. sensor
DFS
24 VAC hot return from Dirty Filter Switch
(upper pin)
DFS
24 VAC hot out for Dirty Filter Switch
(lower pin)
APS
24 VAC hot return from Air Proving Switch
(upper pin)
E
APS
24 VAC hot out for Air Proving Switch
(lower pin)
C
Common for the VFD output
2-10 VDC (0-100%) output for the indoor blower Variable
VFD
Frequency Drive
VFDFLT
24 VAC hot input from the normally open VFD alarm contact
Table 47: Smart Equipment™ UCB - USB connector
Location
Label
J10
Type A female Universal Serial Bus connector
F
J15
Factory wired SA Bus connector
Table 48: Smart Equipment™ UCB - 24 V terminal
Location
Label
G
24 V FOR OUTPUTS
Table 49: Smart Equipment™ UCB - heat section connections
Location
Label
H1
24 VAC hot output for heat section stage 1
H2
24 VAC hot output for heat section stage 2
H
MV
24 VAC hot input confirming heat section operation
Table 50: Smart Equipment™ UCB - pin cooling and fan output
Location
Label
CN-FAN
24 VAC hot output for the condenser fan contactor coil
AUX HGR
24 VAC hot output for hot gas reheat components
24 VAC hot output for indoor blower contactor coil/indoor
FAN
blower VFD enable relay coil
I
C1
24 VAC hot output for compressor 1
C2
24 VAC hot output for compressor 2
Description
Description
Description
24 VAC hot for H1, H2, CN-FAN, AUX HGR, FAN C1 and C2
output relay contact switching
Description
Description
Johnson Controls Ducted Systems
Function and comments
Input required for reheat units, optional in all other units, may be a communicated
value. Used in return air enthalpy calculation, temperature/humidity setpoint reset,
reheat operation.
Input required for variable air volume units. Used in VAV indoor blower operation.
Optional input; switch closure for greater than 15 seconds during indoor blower
operation initiates a notification alarm
Connects through circuit trace to the R terminal
When this optional input is enabled: the air proving switch must close within 30
seconds of initiation of indoor blower operation and not open for greater than 10
seconds during indoor blower operation to allow heat/cool operation and prevent an
"APS open" alarm; the air proving switch must open within 30 seconds of termination
of indoor blower operation to prevent an "APS stuck closed" notification alarm
Connects through circuit trace to the R terminal
Negative of the VDC circuit for the VFD output
Output is active with indoor blower operation. For CV units: this output provides
stepped IntelliSpeed control of the indoor blower VFD based on fan-only, cooling stage
and heating stage outputs. For VAV units: this output provides control of the indoor
blower VFD based on supply duct static pressure input and setpoint.
The VFD alarm contact switches from R within the unit wiring harness. 24 VAC input
results in unit shutdown and a "VFD fault" alarm
Function and comments
Used for backup, restoration, and copying of board parameters as well as board software
updating through a flash drive
Output relay circuitry is isolated from other UCB components and the 24
VAC hot source may be from a second transformer in the unit
Function and comments
Not effective for cooling-only units. Output if demand is present and permissions allow one
stage or two stages of heat section operation
Not effective for cooling-only units or units with single-stage heat sections. Output if demand
is present and permissions allow two stages of heat section operation
Sourced from gas valve in gas heat units or first stage heat contactor in electric heat units.
Input within 5 minutes from initiation of H1 output initiates the "Heat On Fan Delay" timer,
loss of input following the termination of H1 output initiates the "Heat On Fan Delay" timer,
no input within 5 minutes from initiation of H1 output initiates an "Ignition Failure" alarm,
input for longer than 5 minutes without H1 output initiates a "Gas Valve Mis-wire" alarm
Function and comments
Output with either C1 or C2 output; interrupted during defrost cycle for heat pump
units
Effective only for reheat units, output with reheat operation
Output with heat/cool operation, G input or schedule demand
If demand is present and permissions allow compressor 1 operation; output with
compressor cooling, comfort ventilation cooling, reheat or heat pump heating demands
Not effective for one stage compressor UCBs. If demand is present and permissions
allow compressor 2 operation; output with compressor cooling, comfort ventilation
cooling or heat pump heating demands
INSTALLATION MANUAL ZQ SERIES 3 - 5 ton 60 Hertz R-410A
Function and comments
59