Resetting The Programming Menu Parameters And The Lockout Log - Riello RG2 Installation, Use And Maintenance Instructions

Light oil burners
Table of Contents

Advertisement

Available languages

Available languages

6.8.8
Resetting the programming menu parameters
and the lockout log
The control box allows you to reset the log and the number of
lockouts, the operating hours, the number of ignitions and recov-
er the menu's default, see paragraph "Block diagram for enter-
ing the menu" on page 34.
Sequence for setting and restoring the parameters
 Programming allowed in OPERATING mode and in STAND-
BY.
 Press the button for 40 sec. ≤ t < 45 sec.
 The GREEN LED blinks 7 times.
 Release the button.
 GREEN LED OFF
 Press the button 1 time to reset the lockout log (*)
 Press the button 2 times to reset the number of lockouts (*)
 Press the button 3 times to reset the number of hours oper-
ating with flame (*)
 Press the button 4 times to reset the number of heat
requests (*)
 Press the button 5 times to reset all the default values of the
parameters of the PROGRAMMING MENU (*)
 GREEN LED ON and OFF every time press and release
 After 10 sec., the GREEN LED will blink for the number of
times programmed (0.5 sec. ON; 0.5 sec. OFF).
20136866
Start-up, calibration and operation of the burner
36
GB