Maintenance Position - Riello RG2 Installation, Use And Maintenance Instructions

Light oil burners
Table of Contents

Advertisement

Available languages

Available languages

5.12 Maintenance position

There are two ways to access the nozzle, the diffuser disc and
the electrodes:
1st Method (Fig. 15):
 remove the wires 4) from the control box, the flame sensor
5) and unscrew the nut 3) from the pump.
 Loosen the screws 2) and extract the nozzle-holder assem-
bly 1) by turning to the right.
 Remove the wires 4) from the electrodes, loosen the screw
3)(Fig. 13) and remove the diffuser disc-holder assembly 7)
from the nozzle-holder assembly 1).
 Screw on the nozzle 6) while holding the nozzle holder still
with a spanner.
 Refit following the operations in the reverse order to the one
described above.
2
4
5
6
3
20136866
Installation
1
7
E9317
Fig. 15
20
2nd Method (Fig. 16):
 unscrew and remove the fixing nut to the flange and remove
the burner from the boiler.
 Connect the burner to flange 1), loosen the screws 3) then
remove the blast tube unit 2).
 Remove the wires 4) from the electrodes.
 Replace and correctly screw in the nozzle 6), tightening it as
shown in Fig. 16.
 Refit following the operations in the reverse order to the one
described above.
Having put back the nozzle-holder assembly,
screw in the nut 9), as shown in Fig. 17.
WARNING
2
5
4
S9698
Tighten without
bringing right
to the end stop
GB
3
6
1
Fig. 16
9
Fig. 17
D5684