Electrical Connection To The Terminal Strip - Riello P 140 T/G Installation, Use And Maintenance Instructions

Oil burners, three-stage operation
Table of Contents

Advertisement

Available languages

Available languages

4.2 ELECTRICAL CONNECTION TO THE TERMINAL STRIP

(installer-set)
P 140 - 200 - 300 T/G
DIRECT MOTOR STARTING
(A)
P 300 - 450 T/G
STAR-DELTA MOTOR STARTING
(B)
THERMAL RELAY
(C)
NOTE:
Check the lock-out by darkening the
photo-cell after removal of the cover.
ATTENTION: HIGH VOLTAGE
LAYOUT (A) - Electrical connection P 140-200-300 T/G
burners with direct motor starting
D2568
P 140 T/G
230 V
F
A
25
L
2
2,5
mm
LAYOUT (B) - Electrical connection P 300-450 T/G burners
with star-delta motor starting
D2570
KEY TO LAYOUTS (A) - (B)
I1 - Burner manual stop switch
MA - Star-delta starter terminal strip
MB - Burner terminal strip
PS - Reset push-button
S - Remote lock-out signal
TL - Load limit remote control system:
TS - Safety load control system:
T2 - 2
T3 - 3
SCHEMA (C) - Calibration of thermal relay
This is required to avoid motor burn-out in the
event of a significant increase in power
absorption caused by a missing phase.
• If the motor is star-powered, 400 V, the cursor
should be positioned to "MIN".
• If it is delta-powered, 230 V, the cursor should
be positioned to "MAX".
If the scale of the thermal relay does not include
rated motor absorption at 400 V, protection is
still ensured.
46
Cables cross-section
P 200 T/G
400 V
230 V
400 V
25
35
25
2,5
4
2,5
Cables cross-section
P 300 T/G
230 V
400 V
F
A
50
35
L
2
6
4
mm
E
2
4
2,5
mm
shut down the burner when the boiler
temperature or pressure reaches the
maximum preset value
operateds when TL is faulty
nd
stage load control system
rd
stage load control system
P 300 T/G
230 V
400 V
63
50
6
4
P 450 T/G
230 V
400 V
63
50
10
6
6
4