Electrical Connections To Terminal Strip - Riello GI/EMME 400 Installation, Use And Maintenance Instructions

Dual fuel gas-oil/gas burners
Table of Contents

Advertisement

Available languages

Available languages

WITH VALVE PROVING SYSTEM DUNGS VPS
WITHOUT VALVE PROVING SYSTEM
Key to layouts
MB
Burner terminal strip
IN
Manual burner stop switch
PG
Minimum gas pressure switch
S
Remote lock-out signal
S1
VPS lock-out signal
TL
Limit load control system
TR
High-low mode load control system: controls 1st and 2nd operating stage
TS
Safety load control system
VPS Valve proving system
V1
1st stage gas shut off valve
V2
2nd stage gas shut off valve
VS
Gas safety valve
Notes
• Leads minimal section: 1,5 mm
• To verify the lock-out obscure the U.V. detector.
• For continuos-operation, safety standards require a compulsory stop every 24 hours, controlled by a special mon-
itored switch connected in series with the load control devices (TL and IN).
• The flame modulation is obtainable trought the 2nd stage remote control system TR, connected to the terminals 6 - 7.

ELECTRICAL CONNECTIONS TO TERMINAL STRIP

(as set up by the installer)
2
.
D1958
20